Operational Tests
External Timing Verification
5 - 2 2
Lucent Technologies - Proprietary
See notice on first page
365-372-327 R2.0
Issue 1, October 2003
Figure 5-1
Metropolis
®
DMXtend Shelf Backplane
............................................................................................................................................................................
Step 11
Click
Send
to issue a second
rtrv-syncn
command.
Result:
The
Response Window
should display the command
followed by a
COMPLD
indication as well as indicating that the other
reference is now the active reference.
............................................................................................................................................................................
Step 12
Reconnect the timing cable at the rear of the shelf.
Requirement:
The
MN
LED extinguishes on the SYSCTL and the
FAULT
LED on the OLIU stops flashing.
............................................................................................................................................................................
Step 13
Check off the appropriate box in Appendix E, Installation Checklist.
...........................................................................................................................................................................
End of Steps