Operational Tests
Miscellaneous (Environmental) Discrete
Telemetry Test
5 - 2 4
Lucent Technologies - Proprietary
See notice on first page
365-372-327 R2.0
Issue 1, October 2003
............................................................................................................................................................................
Step 8
Click
Send
to issue the command.
Result:
The Response Window should display the command
followed by a
COMPLD
indication as well as indicating the correct
environmental alarm has been activated.
............................................................................................................................................................................
Step 9
Remove the short and verify that the minor (
MN
) alarm indication on
the SYSCTL clears.
............................................................................................................................................................................
Step 10
Repeat Step 3 through Step 9 for each environmental input being used.
............................................................................................................................................................................
Step 11
Check off the appropriate box in Appendix E, Installation Checklist.
...........................................................................................................................................................................
End of Steps