Equipment and Cable Installation for Metropolis
®
DMXtend
Shelf Horizontal Bay Mount
Planning
...........................................................................................................................................................................................................................................................
1 - 5
Lucent Technologies - Proprietary
See notice on first page
365-372-327 R2.0
Issue 1, October 2003
Table 1-1, Cable Requirements and Options lists available cables along
with the required number (if any).
Notes:
1. One -48VA and -48VB main power feeder is required per shelf. The shelf
requires the use of a right angle power connector on each feed.
2. One CIT Cable Assembly is required for PC interface with the
Metropolis
®
DMXtend (not included with equipment).
3. Two DS1 Cable Assembly are required for each D or G Function Unit
group that will support additional DS1 traffic using the LNW8 (R1.1).
Each DS1 Cable Assembly consists of two separate cable assemblies, both
containing 28 pairs of 24 gauge cable. One cable is for input and the other
cable is for output.
4. One DS3 Cable Assembly is required for each D or G Function Unit group
that will support 12 DS3’s of traffic. Each DS3 Cable Assembly consists
of two separate cable assemblies, both containing 735A cables. One cable
consists of 12 inputs and the other cable consists of 12 outputs.
5. Two DS3 Cable Assembly are required for each D or G Function Unit
group that will support additional DS3 traffic using the LNW19. Each
DS3 Cable Assembly consists of two separate cable assemblies, both
containing 735A cables. One cable consists of 24 inputs and the other
Table 1-1
Cable Requirements and Options
Cable Assembly Description
Required
See Note
Power
Yes
CIT
Yes
DS1 Optional
DS3 Optional
DS1/DS3 Hybrid
Optional
X.25 - X.25
Optional
X.25 - Switch (AISW)
Optional
Office Alarm
Optional
Office Alarm Mult
Optional
Miscellaneous Discrete
Optional
LAN 10BASE-T (Crossover)
Optional
LAN 10BASE-T (Straight
Through)
Optional
Sync Timing
Optional
Modem Optional