Equipment and Cable Installation for Metropolis
®
DMXtend
Shelf Horizontal Bay Mount
DS1 and DS3 Hybrid Cable Installation
...........................................................................................................................................................................................................................................................
1 - 3 9
Lucent Technologies - Proprietary
See notice on first page
365-372-327 R2.0
Issue 1, October 2003
............................................................................................................................................................................................................................................................
DS1 and DS3 Hybrid Cable Installation
Description
This section describes how to connect the DS1 and DS3 Hybrid cables
to the Metropolis
®
DMXtend shelf and route the cables out of the bay
and to the DS1 and DS3 Hybrid Cable terminating equipment. Perform
this procedure if DS1 and DS3 Hybrid cables are required.
It should be noted that the cables used for DS1 and DS3 Hybrid support
are a combination of 28 DS1 pair DS1 cable and 3 coaxial DS3 cables
(12 port).When using the LNW39 DS1/DS3/16/3 pack only the first 16
DS1 pairs of the cable will be used in addition to the 3 DS3 cables.
Important!
When cabling the Metropolis
®
DMXtend to a DSX,
the DSX becomes an extension of the Metropolis
®
DMXtend
backplane connections. Therefore, the IN on the Metropolis
®
DMXtend backplane connects to the IN of the DSX and the OUT of
the Metropolis
®
DMXtend backplane connects to the OUT of the
DSX respectively
DS1 and DS3 Hybrid cable options are listed in Table 1-9, DS1 and
DS3 Hybrid Cable Assemblies (page 1-42).
DS1 and DS3 Hybrid Cable transmission connections are in
Table 1-10, DS1 and DS3 Hybrid Cable DS3 Transmission
Connections (page 1-43).
............................................................................................................................................................................
Procedure
Step 1
Refer to the engineering job specification. Obtain the DS1 and DS3
Hybrid cables per Table 1-9, DS1 and DS3 Hybrid Cable Assemblies
(page 1-42) and note the function group where each cable will be used.
Label the cables, indicating bay, shelf, function group (A and B) and
direction (IN or OUT of the bay) at each end.
............................................................................................................................................................................
Step 2
Connect the function group A/B cables at the Metropolis
®
DMXtend
end, carefully matching the correct connector with the appropriate