Equipment and Cable Installation for Metropolis
®
DMXtend
Shelf Horizontal Bay Mount
DS1 and DS3 Hybrid Cable Installation
1 - 4 0
Lucent Technologies - Proprietary
See notice on first page
365-372-327 R2.0
Issue 1, October 2003
backplane connectors as shown in Figure 1-13, DS1 and DS3 Hybrid
Cable Connections (page 1-40).
Important!
The DS1 and DS3 Hybrid Cable only supports slots
A1/B1 and A2/B2 and only connects to J5A/B (IN) and J6A/B
(OUT).
Figure 1-13 DS1 and DS3 Hybrid Cable Connections
............................................................................................................................................................................
Step 3
Route the cables along the backplane and out of the bay to the DSX per
Figure 1-14, DS1 and DS3 Hybrid Cable Routing (page 1-40).
Figure 1-14 DS1 and DS3 Hybrid Cable Routing