363-205-401
Power Up: DLP-513
Issue 7, March 1997
Page 3 of 8
6.
NOTE:
The four plugs supplied to upper two battery shelves (battery string 2) are
labeled P5, P6, P7, and P8.
Connect each battery lead jack to one of two plugs supplied to each shelf.
7.
Get DMM and condition to measure DC volts.
8.
In battery section of cabinet at power panel, refer to Table A and connect DMM
test leads to +BAT TEST jack J1 or J3 and
−
BAT TEST jack J2 or J4 of bat-
tery string 2.
9.
Does meter indicate greater than 45.0 volts DC?
If YES, then proceed to Step 18.
If NO, then continue with Step 10.
10. Check battery lead connections at battery shelf.
11. Does meter indicate greater than 45.0 volts DC?
If YES, then proceed to Step 18.
If NO, then continue with Step 12.
12.
NOTE:
If voltage requirements are not met after replacement battery pack is
installed, original battery pack should be reinstalled in battery shelf.
Replace one of the battery packs in battery shelf.