9.
Place all twelve batteries in the battery compartment as shown in Figure 1.
Figure 1 – Layout of Lineage 2000 VR Series Batteries in 80D Cabinet
10. Coat inter-battery bus bars with NO-OXid grease and install on the batteries as
shown in Figure 2. Install 1/4 inch lock washer and nut on battery post. Using
insulated torque wrench with the socket, tighten nut to 55 in-lbs torque. Repeat
for each battery post until all 12 batteries are connected together.
Comment:
For battery string 3 the 12 batteries are connected in 2
groups of 6 batteries. A cable connects + of battery 6 to - of
battery 7 using the hardware to connect the inter-battery bus
bar.
Cable
Patch
Top View
Side 2
6
7
1
2
12
1
2
- +
- +
6
String #2
String #3
8
9
10
9
10
11
11
12
1
2
3
4
5
6
7
8
Interbattery Bus Bar
To Side 2
3
4
5
- +
- +
- +
- +
- +
- +
Side 1
6
7
8
- +
- +
9
- +
- +
- +
- +
- +
3
4
5
2
1
- +
11
12
- +
Front View
- +
10
Battery String Cable
String #1
3
4
5
3
4
1
2
5
6
7
8
9
10
11
12
String #3