363-205-401
RT Turn Up: DLP-506
Issue 7, March 1997
Page 5 of 8
Response:
After approximately 1 minute, all indicators will go off. MISC( )
may be lighted. Clear power shelf trouble if you have a
MJ/MN NE alarm using 363-205-500 Maintenance TOP.
12.
!
CAUTION:
Incorrect ADU option switch settings can cause service interruptions. Do
not change any option switches except the ones listed for equipping
digroups. For FPB Mode 1 systems, removing the ADU will interrupt
service on digroup A. Therefore, this procedure requires that a Mode 1
system has all digroups equipped.
NOTE:
If the ADU you are installing is a replacement, the system configuration
(S1 through S11) options must be set as directed in the previous Steps.
Remove ADU (Figure 1) from bank being equipped.
13. Set switch S1 positions 5 and 6 as follows;
• 5 - Toward ABE to option digroup(s) AB equipped.
• 6 - Toward CDE to option digroup(s) CD equipped (if required).
14. Set NORM/CLEAR option plug for NORM option (center and top pins).
15. Have a CTU and/or DTU already been installed in the dual bank assembly?
If YES, then continue with Step 16.
If NO, then proceed to Step 26.
16.
NOTE:
This procedure assumes the TRU and LIU slots for the digroup(s) (AB or
CD) being equipped have not been installed.
!
CAUTION:
Incorrectly set ADU option switches may result in immediate or future
loss of service or may introduce errors into the digital bitstream.
Reinstall ADU into ADU slot.
17. After approximately 15 seconds, are ADU MJ and NE and BCU A, B
DIGROUP indicators lighted (BCU C, D DIGROUP indicators will also be
lighted if CD digroups are in the preservice and equipped state)?
If YES, then STOP. YOU HAVE COMPLETED THIS PROCEDURE.
If NO, then continue with Step 18.