RT Turn Up: DLP-520
363-205-401
Page 2 of 2
Issue 7, March 1997
7.
Release OPEN BAT TEST pushbutton.
8.
Did DMM indicate 0 mV for any battery string?
If YES, then continue with Step 9.
If NO, then STOP. YOU HAVE COMPLETED THIS PROCEDURE
9.
Check battery string connections (refer to SD-7C158-01). Check battery com-
partment to verify that battery string is connected to cables from control & dis-
tribution panel. Check the fuse in each battery cable from the control &
distribution panel and make sure it is not blown. (Be sure to check the positive
and negative battery cable for each battery string.) Fix connection problem
and repeat from Step 4.