Conversions: DLP-506
363-205-401
Page 2 of 6
Issue 7, March 1997
Table A
AUB27 Switch Setting
Function
S1 Switch Position
Function
No Protection Line (
NPL)
1
Protection Line (
PL)
Mode 2 Operation (
2)
2
Mode 1 or FPC Operation (
4)
(Always Use
4 Unless Equip-
ping FPB Mode 2)
AB In-Service (
ABI)
3
AB Pre-Service (
ABP)
CD In-Service (
CDI)
4
CD Pre-Service (
CDP)
AB Equipped (
ABE)
5
AB Unequipped (
ABU)
CD Equipped (
CDE)
6
CD Unequipped (
CDU)
Major Alarm for MISC1 (
1MJ)
7
Minor Alarm for MISC1 (
1MN)
Major Alarm for MISC2 (
2MJ)
8
Minor Alarm for MISC1 (
2MN)
Function
S2 Switch Position
Function
16 Bit Alarm Field (
16)
1
13 Bit Alarm Field (
13) (Al-
ways Use
13)
FS Framing (
FS) * (Use FS
for FPB Mode 1 or 2)
2
ESF Framing (
FE) † (Use FE
for FPC-AutoCut)
No Cutover Hunting (
NC)
(Use
NC for Mode 1 and 2 or
When FPC-AutoCut is in
Pre-Service)
3
Cutover Enabled (
CUT) (Only
Use
CUT When Establishing
End-to-End FPC-AutoCut
System)
(
SGL)
4
(Always Use
DBL)
(
PA)
5
(Always Use
NPA)
(
MJP)
6
(Always Use
MNP)
Function
S3 Switch Position
Function
Data Link (
DL) (Always Use
DL)
No Data Link (
NDL)
Function
Clear Norm Position
Function
Clear Provisioning (Use
CLEAR When ADU is First
Installed in New System)
Do Not Clear Provisioning
(Use
NORM for In-Service
System)
S4, S5, S6, S7
Rotary Switches
S8, S9, S10, S11
System ID Number
(Always Set to 0)
* Use FS option for FPB Mode 1, Mode 2, and for integrated applications.
† Use FE option for FPC-AutoCut and FPC applications.