Conversions: DLP-508
363-205-401
Page 4 of 4
Issue 7, March 1997
12. Are switch settings on option switch correct?
If YES, then continue with Step 13.
If NO, then proceed to Step 14.
13. Get another ADU and set switches on option switch S1 according to work
order and Step 3.
14.
!
CAUTION:
Incorrectly set ADU option switches may result in immediate or future
loss of service or may introduce errors into the digital bitstream.
Insert ADU into ADU slot in bank being equipped.
Response:
After approximately 20 seconds, ADU and BCU FAIL indica-
tors go off.
15. After approximately 20 seconds, do ADU and BCU FAIL indicators go off?
If YES, then STOP. YOU HAVE COMPLETED THIS PROCEDURE.
If NO, then continue with Step 16.
16. Correct setting of switches on option switch and repeat from Step 6.