Power Up: NTP-003
363-205-401
Page 2 of 4
Issue 7, March 1997
DO ITEMS BELOW IN ORDER LISTED
FOR DETAILS, GO TO
2.
Get Support Apparatus Listed:
• 216-type tool (80-type cabinet only),
• Special key (allen-type wrench) - COMCODE 846244168
(51-type and 80-type cabinets only),
• DMM (digital multimeter) with an accuracy of 1.0% and an
ac/dc input impedance of
≥
1 megohm.
• One AUA11( ) PCU (power converter unit).
3.
!
CAUTION:
An electrostatic discharge wrist strap with a minimum
resistance of 250K Ohms should be worn when handling
Series 5 circuit packs to prevent possible damage to the
circuit packs. Before using the wrist strap, check it for opens,
shorts, and minimum resistance value. If the strap does not
pass these checks it should not be used. To avoid possible
personal injury while using the wrist strap, do not connect it
to the power shelf or adjacent portions of the RT frame.
Connect the wrist strap to ESD GRD jack on the fan unit, if
present. If grounding jack is not present, connect wrist strap
to bare-metal section of the frame well away from the power
shelf.
Verify AC power panel connections for power shelf has been
made and turn on circuit breaker(s).
4.
Install LDU (load distribution unit) in power shelf.
5.
If RT backup power is from 337A BATTERY
CHARGER(s)/KS-21906, L4 battery packs, continue with Step 6.
Otherwise, proceed to Step 9.