363-205-401
Power Up: DLP-504
Issue 7, March 1997
Page 3 of 6
6.
Batteries are on high charge and may require up to 24 hours to charge. Do not
perform this procedure until HIGH RATE CHG/ON indicator on BATTERY
CHARGER goes off.
7.
!
CAUTION:
Service interruption will occur if batteries are disconnected and AC power
is not available.
Disconnect battery leads of batteries to be tested from battery shelf.
8.
NOTE:
Under normal conditions, when the first battery is connected, the
following occurs: (a) The test set TIME display indicates 00 MIN:00 SEC;
(b) The status display indicates which test set BATT plug the battery is
connected to, status of the battery (GOOD or REPLACE), and the
READY indicator lights; (c) Test set fan operates.
At test set connector head (Figure 1), connect battery leads (up to four) to
BATT 1, 2, 3, and 4 plugs.
9.
NOTE:
If status display does not indicate battery number of battery status, BATT
fuse may be blown, connector head or test set may be defective, or
battery pack may be defective.
Does test set display indicate REPLACE for all batteries being tested?
If YES, then continue with Step 10.
If NO, then proceed to Step 12.
10. Replace all batteries and connect good batteries to battery shelf.
11. Place batteries on high charge by depressing HIGH RATE CHG/ACTIVATE
pushbutton on BATTERY CHARGER and repeat from Step 6.