InstallatIon, operatIon and maIntenance InstructIons

 

  Pressure-relief damPers drK

 

  bacK-draught damPers rsK

Product designation    

DRK-10…., RSK10…. 
          

technical sPecifications

 

Max. size W x H:     

drK:

 2400 mm x 7900 mm

   

rsK:

 7900 mm x 7900 mm (subject to shipping)

Max. slat length:     

1200 mm

Tripping pressure:   

drK:

 acc. to order 

   

rsK:

 no specified tripping pressure

Air flow direction:     

horizontal or vertical acc. to customer order

Free cross section:     

>60 % ((more precise figures after calculation by manufacturer)

ateX

 

 

 

DRK and RSK are only approved in specific designs and with 

 

 

 

appropriate identification for Zones 1, 2, 21 and 22 according 

 

 

 

to ATEX Directive 94/9/EC.

 

 

 

If the fitter or operator changes the dampers in any way, the

 

 

 

ATEX approval becomes null and void. It is important to ensure

 

 

 

that the damper and additional equipment are installed in 

 

 

 

compliance with zoning requirements.

In principle, avoid all damage caused by external influ-
ences. Never lift dampers by the slats or the outer lin-
kages. Dampers with a maximum weight of 50 kg 
can be lifted by the C-profile frame. With heavier dam-
pers, use at least four points at the corner angles as 
suspension points. Do not use individual slats under 
any circumstances as footholds during installation. 
Report any damage, e.g. deformation of slats, dents, 
impacts or warping of the C-profile frame etc. imme-

shiPment

installation

diately to the supplier or manufacturer. This may im-
pair the proper functioning of the damper and at best 
cause dangerous circumstances to occur. 

ateX:

 Under no circumstances may ATEX dampers be 

fitted after a fall or impact with visible or concealed 
damage

These dampers can be fitted or removed to or from a 
wall or an air conditioning system, or integrated in a 
duct section. First make sure the air flow is in the pro-
per direction as indicated by the red arrow on the 
damper housing. Mount the dampers warp-free, ten-
sion-free, on a flat surface and without any angular 
errors in the damper frame. When mounting, use the 
4 corner holes provided as standard. With larger dam-
pers, fit additional flange couplings at spacings of 
200-500 mm. This is the responsibility of the planning 
engineer or fitter. During installation, make sure that 
the slats are exactly horizontal. The damper must be 
adjusted exactly vertically (for horizontal air flow) or 
exactly horizontally (for vertical air flow). 

When installation is complete, check the angle of the 
damper frame. It must be exactly 90°. Correct any de-
viations immediately. In addition check the free move-
ment of the slats, linkage and tripping mechanism. 

Avoid as far as possible any reduction in freedom of 
movement on customer premises when installing insu-
lation materials, installation ducts, auxiliary structures 
etc. If this is not observed, it can lead to considerable 
disruptions in operation, e.g. slats rub against the dam-
per frame, different tripping pressure, damper fails to 
open or close, reduced leak tightness, etc.

On models with side seals (Di, DIN, CEN etc.) protect 
the units from impurities of all kinds during the instal-
lation phase. Drilling swarf and concrete chips can 
damage the side seals. Before starting up the dampers, 
wipe the side seals thoroughly until they are dry.