background image

LER3000 Series – Polyvinyl Exit Sign

3/4

Lumacell

Tel: (888) 552-6467 ext. 547 or 255

Fax: (888) 867-1565

www.lumacell.com

06/04 750.1048 Rev. B

Nexus models

Refer to figure 6 for the wiring of Nexus models.
These units can accept an input voltage of 120 or 347 VAC:

120 VAC — 

Connect the black (120 VAC) lead and white (neutral) lead 

to the building utility. Insulate the red wire.

347 VAC — 

Connect the red (347 VAC) lead and white (neutral) lead to 

the building utility. Insulate the black wire.
Feed excess wire into the junction box.
Leave as much space as possible between the live voltage cabling and 
the unsheathed low voltage data cabling.
Run the double insulation of data cables past the line cabling section and 
only strip back the last 30mm of the data cable sheathing.

Automatic Diagnostics (Self-Powered Models)

There are three diagnostic indicators: one external and two internal. Unit 
must be opened to gain access to internal indicators.       
External: General alarm, “Service Required”. The LED will blink if any 
alarm condition is detected (see fig. 7).
Internal: Battery Alarm & Charger Alarm. Steady ON if alarm condition 
exists (See fig. 8).

Normal operation, No fault — 

“Service Required” is OFF and one of 

the two internal LED blinks, showing that the micro controller is active.

Faulty operation — 

“Service Required” blinks.

Battery Alarm ON, Charger Alarm OFF: Check battery or replace battery.
Battery Alarm ON, Charger Alarm ON: Check LED strip.
Battery Alarm OFF, Charger Alarm ON: Check charger circuit.

Nexus models

Nexus models use two local indicators. One is a green LED for AC pilot 
lamp. The other is a tricolor LED (Service) which identifies and displays 
the Nexus status. The table below describes each status: 

Nexus Tricolor LED  — 

Status table

Maintenance (All Models)

None required. If AC supply to the unit is to be disconnected for 2 
months or more, the battery must be disconnected, Self-Powered Mod-
els only.

Canopy

Figure 6

LED Strip

Nexus data 

Black (120)

Red (insulate)

White (neutral)

Black (insulate)

White (neutral)

Red (347)

120 VAC        or        347 VAC

Sign

30 mm

Interface

Data

Tape

Nexus data cables

Nexus data

Nexus

Transformer

Nexus model wiring

terminal block

cables

Figure 7

Figure 8

 Battery Alarm

Charger alarm

Diagnostic board

Uncommissioned

Commissioned

Normal

Red/Off pulsing

Green steady

Under test

N/A

Green/Off pulsing

Wink mode

Yellow-orange/(red or off) pulsing

Yellow-orange/Off pulsing

Neuron faulty

Red Steady

Red steady

Power fail

Off

Off

Battery disconnected

N/A

Off

Summary of Contents for LER3000 Series

Page 1: ...of wire length c Remove proper knockouts in canopy backplate for desired mounting position For Nexus option install the liquid tight fitting provided with the unit For Ceiling mount use the k out located on side of the unit opposite side of the diagnostic display For Side mount use the k out located on top of the unit see fig 4 d Feed unswitched AC wires through large hole in canopy mount ing plat...

Page 2: ... Connect the white lead to neutral and the purple lead to AC line volt age the input is universal 110 to 347 VAC See fig 5 Optional For AC models used with DC remote power the sealed DC nipple wire assembly 2 wires will also need to be installed One end connects to the LED STRIP leads inside the enclosure and the other end to DC input inside the junction box Connect the red lead to positive and th...

Page 3: ...mal operation No fault Service Required is OFF and one of the two internal LED blinks showing that the micro controller is active Faulty operation Service Required blinks Battery Alarm ON Charger Alarm OFF Check battery or replace battery Battery Alarm ON Charger Alarm ON Check LED strip Battery Alarm OFF Charger Alarm ON Check charger circuit Nexus models Nexus models use two local indicators One...

Page 4: ...lready be installed 4 Install the diffuser panel by snapping the top edges under the two top retention screws and then snapping the bottom edges under the two bottom retention screws see fig 11 5 The EXIT panel installs in the same manner if required remove the appropriate chevron 6 Install the lens by using the 4 short and 2 long tamper proof screws see fig 12 The tamper proof screws should be eq...

Reviews: