background image

Lumacell

Tel: (888) 552-6467 ext. 547 or 255

Fax: (888) 867-1565

www.lumacell.com

04/03 750.1031 Rev. A

LER900 – Exit sign

1/2

LER900 – Exit sign

AC & Self-Powered model

IMPORTANT SAFEGUARDS

When using electrical equipment, basic safety precautions should 
always be followed including the following:

READ AND FOLLOW ALL SAFETY 
INSTRUCTIONS

1. Do not use outdoors.
2. Do not let power supply cords touch hot surfaces.
3. Do not mount near gas or electric heaters.
4. Use caution when handling batteries. Avoid possible shorting.
5. Equipment should be mounted in locations and at heights where it 

will not readily be subjected to tampering by unauthorized personnel.

6. The use of accessory equipment not recommended by the manufac-

turer may cause an unsafe condition.

7. Do not use this equipment for other than intended use.
8. All servicing should be performed by qualified service personnel.

SAVE THESE

 

INSTRUCTIONS

Installation Instructions

1. Turn off AC power.
2. Route an unswitched AC circuit of rated voltage into the junction box 

and leave 6” of wire length.

3. Follow the proper installation procedure.

Ceiling mount and End mount (with canopy)

a.   Determine desired mounting location of sign (see fig. 2).
b. Route AC wires, and DC wires if applicable, from exit through the 

canopy.

c. Mount the spider plate provided to the junction box using the 

junction box screws.

d. Attach incoming ground to the ground wire provided in the exit 

sign.

e. Make the proper connections (see fig. 5). 

120 VAC — 

Connect the black (120) and white (neutral) leads to 

the building utility. Insulate the red wire.

347 VAC — 

Connect the red (347) and white (neutral) leads to 

the building utility. Insulate the black wire.

277 VAC (optional) — 

Connect the orange (277) and white (neu-

tral) leads to the building utility. Insulate the black wire.
Push back the excess wires into the junction box.

f. Fasten the canopy-exit assembly to the spider plate using the 

#8-32 x 1” screws provided.

Part List

1. Junction box (not provided)
2. Spider plate
3. Junction box screws (not 

provided)

4. Canopy screws 1” (2)
5. Back cover (or second front 

cover, double-sided units)

6. End cap (2)
7. End cap screw (4)
8. Canopy
9. Canopy screw 3/8” (2)
10. Front cover
11. Diffuser (2 if the exit sign is 

double-sided)

Figure 1

Figure 2

Reviews: