17
Symbol of terminal
group
Terminal description
1
Connection sockets of the measuring package
(
L1, L2, L3, N
)
Measured quantity:
– current:
1 A
or
5 A,
– voltage:
57.7 V a.c. / 100 V a.c.
or
230 V a.c. / 400 V a.c.
or
400 V a.c. / 690 V a.c.
2 and 3
Connection sockets:
Alarms (
AL 1..6
) - 6 relays
NO
Binary inputs (
BI 1..12
)
– 12 inputs
Analog outputs (
AO 1..4
)
– 4 outputs
L, N, PE
Connection sockets of the supply voltage:
85..230..253 V a.c./d.c.
24 V d.c. / 30 mA
Auxiliary supplies destined to supply external systems
RS485(1), RS485(2),
Ethernet
Communication interfaces: RS485 Modbus Master,
RS485 Modbus Slave, Ethernet 10-Base-T
Earthling functional terminals to connect screens
4.3.1. Mounting of the Power Supply Filter
In order to fulfill EMC requirements, one must always apply the delivered power
supply filter when connecting the supplying wire to the analyser.
To mount the power supply filter one must reeve all the three supplying wires
(L,N,PE) through the filter core, creating a full loop around it (Fig.4.4).