48
downwards for the selected probability
– Max deviation (X%): admissible U RMS deviation percentage
upwards for the selected probability
– Default settings: manufacturer’s settings for the given parameter
group
2
10 sec. frequency limits: configuration of frequency quality parameters for
10 seconds’ periods (default settings acc. to EN 50160):
– Min deviation (100%): setting of the admissible frequency deviation
percentage downwards, for a 100% probability
– Max deviation (100%): setting of the admissible frequency deviation
percentage upwards, for a 100% probability
– Time deviation (X%): setting of the time percentage in which, the
frequency has to be situated in definite limits
– Min deviation (X%): setting of the admissible frequency deviation
percentage downwards, for the selected probability
– Max deviation (X%): setting of the admissible frequency deviation
percentage upwards, for the selected probability
– Default setting: manufacturer’s settings for the given parameter
group
3
Time limits (selection of the counting time):
Weekly (input time) - counted from the selected day of the week with the
definite time of daily reset
Weekly (Power on time) - counted since the analyzer switching on
7
Setting acceptance
7.5.2. Parameter Programming: Dips
7
6
5
4