Power Quality Analyzer User’s Guide
46
Chapter 5 Specifications
5.1 Frequency Measurement
Nominal frequency
Measurement
range
Resolution Accuracy
50Hz 42.50~57.50
Hz
0.01Hz
±0.01Hz
60Hz 51.00~69.00
Hz
0.01Hz
±0.01Hz
400Hz 320~480Hz
0.01Hz ±0.01Hz
Note: measured on Reference Voltage Input
L1/A
.
5.2 Voltage Input
Numbers of input
4 (3 phase + neutral)
Max continuous input
voltage
1000Vrms
Range of nominal voltage
Selectable, 1V to 1000V according to IEC61000-4-30
Max pulse peak voltage
6kV
Input impedance
4M
Ω
5.3 Current Input
Numbers of input
4 (3 phase + neutral)
Type
Clamp Current Sensor, with mV output
Max input voltage
10V
Input range
According to current clamps
Input impedance
100k
Ω
5.4 Sampling System
Resolution
8 channels 16 bits AD
Sampling rate
163.84kS/s Typ. (nominal frequency), 8 channels
sample synchronously
RMS sampling
4096 points for 10/12 cycles (according to IEC 61000-4-
30)
PLL sync
4096 points for 10/12 cycles (according to IEC61000-4-
7)
5.5 Measuring Modes and Parameters
Measurement mode
Measured parameters
Oscilloscope
Vrms
、
Arms
、
Vcursor
、
Acursor
、
Hz
Voltage/Current/Frequency Vrms
、
Vpk
、
Arms
、
Apk
、
CF
、
Hz