background image

NS5-09B

  

User's manual

 

   

                     

32 

 

 

10

 

FIRMWARE UPGRADE 

 

NS5 meters have a feature that allows the user to upgrade the software using a PC with eCon 
software. Free eCon software and update files are available at www.lume.com.pl. Software 
update of the meter (firmware) can be performed via RS485 interface. The update is done in 
LUMEL UPDATER tab. 

 
 

 

 a) 

 b)  

 

Fig.22. View of program window: a) eCon, b) firmware upgrade  

 

Caution! 

After upgrading the software, the user should set the factory settings of the meter, 

therefore it is recommended to preserve the initial meter parameters before the upgrade with 
the use of eCon software. 
After starting eCon the serial port, speed, mode and meter address should be set in the 
settings. Then select NS5 meter and click 

Configure

 To read all the settings, click the down 

arrow, then the floppy icon to save the settings to a file (to restore them later). After selecting 

Update firmware

 (in the upper right corner of the screen)

 Lumel Updater

 (LU) window will 

open - Fig. 22 b. Press 

Connect

.  

Messages

 information window contains info about the 

progress of the upgrade process. When the port is properly opened the display shows: 

Port 

opened

. There are two ways to enter the upgrade mode: remotely through the LU (based on 

settings in eCon - address, mode, speed, COM port) and by turning on the meter power by 
pushing the button 

 (when entering the bootloader mode with the button, communication 

parameters:  speed 9600, RTU8N2, address 1).

 

The display will show boot with bootloader 

version, and LU program will show the message 

Device found 

and the name and program 

version of the connected device. Press the ”

...

  button and select the meter update file. When 

the file is properly opened the following message is displayed 

File opened

. Press 

Send

 button. 

After successful upgrade the monitor switches to normal operation, and the information 
window shows 

Done

 and the upgrade duration. After closing the LU window, go to 

Service 

Parameters

, select 

Set Meter Defaults

 and press the 

Restore

 button. Then press the folder 

icon to open the previously saved settings file and press the up arrow to save the settings in 
the meter. The current software version can also be checked by reading the greeting 
messages of the meter after powering up. 

Caution!

 Turning off the power during the software upgrade may result in permanent damage 

to the meter!  

 

Summary of Contents for NS5

Page 1: ...SERVICE MANUAL SYNCHRONIZING METER NS5...

Page 2: ...ONFIGURATION OF THE METER 11 PARAMETERS 11 7 1 Measurement 13 7 2 Parameters 13 7 3 Relays 15 7 4 Ethernet 17 7 5 Modbus 18 7 6 Settings 19 7 7 Information 19 8 SERIAL INTERFACES 20 8 1 RS485 INTERFAC...

Page 3: ...the network and the generator frequency The synchronization point i e the moment when the frequency voltage and phase values of the generator and the network are equal is indicated by green indicator...

Page 4: ...the meter housing always turn the supply off and disconnect the measurement circuits Removal of the meter housing during the warranty period voids the warranty The synchronizing unit meets the requir...

Page 5: ...ig 3 Overall dimensions of NS5 meter 5 DESCRIPTION OF THE INSTRUMENT 5 1 Voltage inputs Voltage inputs are galvanically isolated internal transformers Un voltages phase or phase to phase are automatic...

Page 6: ...NS5 09B User s manual 6 5 2 External connections diagram External connections are shown in Figures 4a 4b Fig 4a Connections of the synchronizing unit phase measurement voltages Ethernet Option...

Page 7: ...NS5 09B User s manual 7 Fig 4b Connections of the synchronizing unit phase to phase measurement voltages 6 NS5 PROGRAMMING 6 1 General description Fig 5 Front panel Ethernet Option...

Page 8: ...et lead in time Output signals relay contacts AL fault relay is activated in case of faulty external circuit connection when a fault occurs and if the measured values are outside the measuring range S...

Page 9: ...zation The spin speed and direction correspond to the difference between the network and the generator frequency Fig 7 Screen when synchronization conditions are met The values of measured parameters...

Page 10: ...phase shift range on the bar graphs screen 180 180 o 6 2 Starting operation When power is turned on the synchronizing unit displays the logo NS5 meter name version current firmware version and MAC fo...

Page 11: ...figuration of parameters of the meter Relays configuration of SYNC and AL relays Ethernet configuration of Ethernet interface parameters Modbus configuration of RS485 interface parameters Settings set...

Page 12: ...000 Gateway Address 000 000 000 000 DNS Address 008 008 008 008 MAC Address aa bb cc 00 21 01 Acquired from DHCP or entered manually when DHCP is deactivated Modbus TCP Address 001 Port 00502 Max conn...

Page 13: ...m or minimum values is done by pressing the button 7 2 Parameters In this group the parameters of the meter are set To enter the Parameters group press the button for about 3 seconds and then using th...

Page 14: ...he digit with the button or The active position is indicated by the cursor The selected characteristic or value of the parameter should be confirmed by pressing the button or canceled by pressing the...

Page 15: ...the value is too high or to the minimum value when the value is too low To configure NS5 synchronizing unit you can also use the free eCon software available at manufacturer s website 7 3 Relays Selec...

Page 16: ...relay switching delay 0 9 Pulse mode No Yes permanent switching switching pulse No 10 Width of the switching pulse ms 0 999 ms 0 11 Input signals BLK START Active Inactive Graphic illustration of BLK...

Page 17: ...SYNC relay not energized despite meeting synchronization conditions BLK signal did not change its status from 1 to 0 Fig 14 Graphic illustration of BLK and START input signals control with SYNC synch...

Page 18: ...255 255 255 255 255 0 0 1 5 Gateway Address 0 0 0 0 255 255 255 255 0 0 0 0 6 DNS Address 0 0 0 0 255 255 255 255 10 0 0 44 7 MAC Address Aa bb cc 00 21 01 8 Modbus TCP Address 1 247 1 9 Port 80 3200...

Page 19: ...ams No Yes No Fig 17 Screens of Settings group 7 7 Information Select Information group in the options and confirm by pressing the button Fig 18 Screen of Information group Table 6 No Parameter name C...

Page 20: ...r of read registers in one query 61 registers 4 byte 122 registers 2 byte implemented functions 03 04 06 16 17 03 04 registers reading 06 one register record 16 n registers record 17 device identifica...

Page 21: ...Value from the register 1B5B 7003 Check sum CRC B3 B2 B1 B0 B3 B2 B1 B0 01 03 08 41 20 00 00 42 C8 00 00 E4 6F Example 3 Readout of 2 32 bit registers of float type as a combination of 2 16 bit regist...

Page 22: ...ster 1D4D 7501 Check sum CRC B3 B2 B1 B0 B3 B2 B1 B0 01 03 08 41 20 00 00 42 C8 00 00 E4 6F Readout of single register code 06h Example 5 Record of 543 0x021F value to register 4000 0x0FA0 Request Add...

Page 23: ...nchronizing units in the NS5 XX2XXXX version are equipped with Ethernet interface that allows for connection of the synchronizing unit using RJ45 socket to a local or global network LAN or WAN Etherne...

Page 24: ...each pair foiled F FTP twisted pair cable with each pair foiled additionally cable with foil shield S FTP formerly SFTP twisted pair cable with each pair foiled additionally cable with wire mesh shie...

Page 25: ...r special preview of the current measurement values readout of the device status select the language for the Website The access to the Web server is achieved by entering the meter IP address in the we...

Page 26: ...ple http 192 168 1 30 will show the start display in the browser where the user must enter the name and password Fig 21 View of the synchronizing unit web server log window Web server user names canno...

Page 27: ...METER In NS5 meter the data are placed in 16 and 32 bit registers Process variables and parameters of the meter are located in the address space of registers in a manner dependent on the type of the v...

Page 28: ...e generator from above 0 No 1 Yes 1 4013 RW 0 200 10 Acceptable phase shift x 10 20 4014 RW 999 999 ms Lead delay time of SYNC relay switching 0 4015 RW 0 1 Switching pulse 0 permanent switching 1 swi...

Page 29: ...HCP service enabled after powering up or after selecting the menu option APPL or after entering value 1 to register 4099 the meter will automatically receive the IP address subnet mask and gateway add...

Page 30: ...d byte B3 B2 of meter MAC address format B5 B4 B3 B2 B1 B0 4423 R 0 65535 First and zero byte B1 B0 of meter MAC address format B5 B4 B3 B2 B1 B0 4424 R Reserved Device status register 1 address 4415...

Page 31: ...eserved 6024 8024 7512 R Reserved 6026 8026 7513 R Reserved 6028 8028 7514 R Reserved 6030 8030 7515 R Status register 1 6032 8032 7516 R Status register 2 6034 8034 7517 R Reserved 6036 8036 7518 R R...

Page 32: ...the upgrade process When the port is properly opened the display shows Port opened There are two ways to enter the upgrade mode remotely through the LU based on settings in eCon address mode speed COM...

Page 33: ...d quantity Measurement range Resolution Class intrinsic error Voltage Un 50 150 V 150 400 V 20 180 V 60 480 V 1920 kV tr_U 1 0 1 V 0 1 V 0 01 kV 0 2 EN 61557 12 Frequency f 40 45 65 100 Hz 0 001 Hz 0...

Page 34: ...50 Hz 7 68 kHz for 60 Hz Simultaneous sampling across all channels 128 samples per period Real time clock 20 ppm battery of RTC CR2032 Terminals Cross section 0 05 2 5 mm Clamping screws M3 Tightening...

Page 35: ...g unit Electromagnetic compatibility immunity to interference in accordance with EN 61000 6 2 noise emission acc to EN 61000 6 4 Safety requirements according to PN EN 61010 1 standard insulation betw...

Page 36: ...h M other X Acceptance tests without additional requirements 0 with quality inspection certificate 1 With calibration certificate 2 acc to customer s requirements X Un phase or phase to phase voltage...

Page 37: ...NS5 09B User s manual 37 NS5 09B...

Reviews: