31
EN
Parameter Range
Factory
Parameter description
setting
1
sp
0...537
O
C 200
O
C
Set point
32...999
O
F
2
spl
37...149
O
C 120
O
C
Set point for the decreased
100..300
O
F
temperature mode
3
spr
90...160
O
C 90
O
C
Set point for the soft start
194...320
O
F
4
ps
5...100 %
50
Maximal admissible power
delivered to the heater during
the soft start
5
adh
2...20
O
C 10
O
C
Difference between the set value
36...68
O
F
and the temperature above which,
one must signal the alarm
6
adl
2...20
O
C 10
O
C
Difference between the set value
36...68
O
F
and the temperature belowwhich
one must signal the alarm
7
p
1...999 %
4
Proportional band in % of
the measuring range
8
ti
0...999 sek. 120
Integration time-constant
9
td
0...999 sek. 20
Differentiation time-constant
10
seC
0..999
0
Safety code
11
adr
0...247
0
Controller address in the network
12
de9
qC
,
qf
qC
Temperature unit:
O
C -
O
Celsius
O
F -
O
Fahreinheita
13
aua
on
,
off
on
Autotuning algorythm turned On/Off
after the soft start
on
- turned on
off
- turned off
Table 3. List of parameters