background image

ALL PROGRAMMING IS OPTIONAL

Programming is not required for default functionality

•  Set a favorite light level
•  Set high-end and low-end trim for all fixtures 

 Reset Factory Defaults

   Note:

 In some instances, it may be necessary to reset 

the fi xture controls and connected devices back to 
factory default settings. Before beginning, make sure 
that all devices are connected and powered.

A

  Rapidly tap the 

Toggle

 button 

 

u

” 

 on the fi xture 

control three times and hold on the fourth until the 
LED begins to flash slowly; release button.

B

  Within 3 seconds of the start of flashing, again rapidly 

tap the 

Toggle

 button 

 

u

” 

 three times and the LEDs 

will flash rapidly indicating that the unit has been reset 
to factory defaults.

   Note:

 Any associations or programming previously set 

up with the fi xture control will be erased and will need 
to be re-programmed.

Raise

Lower

Favorite

FCC / IC  Information

This device complies with part 15 of the FCC Rules and Industry Canada license-exempt RSS standard(s). Operation is subject to the following two conditions: (1) This 
device may not cause interference, and (2) this device must accept any interference, including interference that may cause undesired operation. Modifications not expressly 
approved by Lutron Electronics Co., Inc. could void the user’s authority to operate this equipment.
NOTE: This equipment has been tested and found to comply with the limits for a Class B digital device, pursuant to part 15 of the FCC Rules. These limits are designed 
to provide reasonable protection against harmful interference in a residential installation. This equipment generates, uses and can radiate radio frequency energy and, if not 
installed and used in accordance with the instructions, may cause harmful interference to radio communications. However, there is no guarantee that interference will not 
occur in a particular installation. If this equipment does cause harmful interference to radio or television reception, which can be determined by turning the equipment off 
and on, the user is encouraged to try to correct the interference by one or more of the following measures:
• Re-orient or relocate the receiving antenna.
• Increase the separation between the equipment and receiver.
• Connect the equipment into an outlet on a circuit different from that to which the receiver is connected.

Set a Favorite Light Level 

(Optional)

 

*

For Pico

®

 remote controls with a 

Favorite

 Button.

PowPak

®

 Controls

Programming

Part of the Energi TriPak

®

 Family

 

A

  Adjust lights to desired level:

Use the 

Raise

 button “

”  

or 

Lower

 button “

” on  

the Pico

®

 remote control.

  

B

  Save favorite level:

Press and hold the 

Favorite

 

button for 6 seconds.

The load will flash 3 times to 
confirm that the Favorite level 
is saved.

Limited Warranty

:

 http://www.lutron.com/TechnicalDocumentLibrary/369-119_Wallbox_Warranty.pdf

 Low-End 

Trim

A

   Enter low-end trim adjustment mode:

 

 Press and hold the 

Lower

 button “

Ǻ

” on the fixture control for 12 seconds.

 

 The lights will flash and the load status LED will begin flashing.

B

  Adjust the low-end trim:

 

 Use the 

Raise

 button “

ŷ

” and 

Lower

 button “

Ǻ

” on the fixture control to adjust and 

set the lights to the desired low-end (1 to 45%).

C

   Save the low-end trim:

 

 Press and hold the 

Toggle

 button 

“ 

u

” 

 for 6 seconds to save setting.

 

 The load status LED will begin flashing and then turn solid to indicate new level has 
been saved.

 High-End 

Trim

A

  Enter high-end trim adjustment mode:

 

 Press and hold the 

Raise

 button “

ŷ

” on the fixture control for 12 seconds.  

The lights will flash and the load status LED will flash.

B

   Adjust the high-end trim:

 

 Use the 

Raise

 button “

ŷ

” and 

Lower

 button “

Ǻ

” on the fixture control to adjust and 

set the lights to the desired high-end (55 to 100%).

C

  Save the high-end trim:

 

Press and hold the 

Toggle

 button 

“ 

u

” 

 for 6 seconds to save setting. 

 

 The load status LED will begin flashing and then turn solid to indicate new level has 
been saved. 

Set Low-End Trim and High-End Trim 

(Optional)

 

*

For best results, minimize the amount of sunlight entering the room before 
performing the following procedures.

   Depending on the fixture manufacturer or load, low-end trim and high-end trim 

may need to be adjusted.

•  

Trim low-end to ensure a stable light level because some loads will flicker or drop 
out if trimmed too low.

•  

Be sure that you can turn on the lights to the low-end trim level without any 
abnormal operation.

•  

The factory default high-end trim is suitable for most applications but can be 
adjusted as desired.

1

Troubleshooting

 

*

 

www.lutron.com

Symptom

Solution

Ballasts / drivers  cannot 
be controlled locally from 
the fi xture control.

•  Ensure that the breaker(s) to the fixture control are energized.
•  Ensure that the fixture control switched hot lead is wired to the ballast / driver (FCJS-010).
•  Ensure that the fixture control control lines (FCJS-010: violet/gray, FCJS-ECO: violet/violet) are 

wired to the ballast / driver.

•  If using FCJS-010, verify the driver/ballast is 0–10 V.  

If using FCJS-ECO, use the Lutron

R

 EcoSystem

R

 driver/ballast.

  Reset to factory defaults.    

Lights do not dim or turn 
ON as expected.

•  Ensure that control lines are wired properly (FCJS-010: violet/gray-polarity-sensitive,  

FCJS-ECO: violet/violet)

•  Ensure that the wires are connected between the fixture sensor and the fi xture control.
• FCJS-010 only: Make sure that 0–10 V

-

  fixture is at low-end (at 0 V), not OFF (at 0 V).  

If OFF (at 0 V), adjust low-end trim.

•  FCJS-010 only: Ensure that fixture does not require an inverted signal (10 – 0 V

-

 control).

•  FCJS-010 only: Verify that the voltage across the gray and violet wires is between 0 and 10 V

-

• FCJS-ECO only: Disconnect the violet / violet wires from the fixture control. Verify that the lights go to 

100%. 

• FCJS-010 only: Disconnect the violet / gray wires from the fixture control. Verify that the lights go to 

100%. Short the violet / gray wires on the ballast / driver, verify that the lights go to low-end. 

Lights do not respond to 
wireless transmitter(s).

•  Ensure that the breaker(s) to the fixture control and ballasts / drivers are energized.
•  Ensure that wireless transmitters are associated to the fixture control.

  Reset to factory defaults.

Wireless transmitter(s) 
cannot be associated to 
the fixture control.

•  The maximum number of wireless transmitters have been associated to the fixture control. To 

remove a previously set up wireless transmitter, tap any button on the wireless transmitter three 
times; on the third tap, hold for three seconds and then tap three more times.

RF range between  
wireless controls is 
diminished below 30 ft 
(9 m).

•  Keep the ballast/driver wiring as short as possible and well organized to avoid excess wire being 

bunched up.

•  Keep the first 7 in - 12 in (20 cm - 30 cm) of the wires coming out of the fixture control knockout 

separated as much as possible from any nearby ballast/driver/lamp wires.

• Contact Lutron

R

 technical support for further assistance.

Lights are unstable at 
low-end.

•  Adjust low-end trim. 

Fixture sensor does not 
turn the lights ON.

•  Check that fixture sensor wires are connected to fixture control.
•  FC-VSENSOR is vacancy only (it will not turn the lights on). 

FCJS-ECO cannot be 
addressed.

•  All drivers/ballasts connected to an FCJS-ECO function as a single zone. If more than one zone is 

required, use RMJS-ECO32-DV-B.

For FC-SENSOR and FC-VSENSOR installation guide visit www.lutron.com

For information on activating egress mode, application suggestions, and many other notes on the 
PowPak

®

 fixture controls, see Lutron

®

 document 048556 or 369866 on www.lutron.com.

NOTE:

 High-end and low-end trim can also 

be performed for a single unit or group of units 
simultaneously with a Pico

R

 remote control. 

For more information see document 
048556 on www.lutron.com.

Technical Assistance  |  1.800.523.9466  

USA, Canada, and the Caribbean

  |  +44.(0)20.7702.0657 

Europe

  |  +1.610.282.3800 

Others

  |  www.lutron.com

     

2

Start Here

Lutron Electronics Co., Inc.
7200 Suter Road
Coopersburg, PA 18036-1299 USA

Lutron, Pico, PowPak, EcoSystem, and Energi TriPak are registered trademarks and Radio Powr Savr and Vive are trademarks of Lutron Electronics Co., Inc. NEC is a registered trademark of the National Fire Protection Association, Quincy, Massachusetts. 
©2014 – 2015 Lutron Electronics Co., Inc.

*

   For set-up, programming, and troubleshooting 

with a Vive

TM

 system, please refer to the installation 

instructions included with the Vive

TM

 hub or at  

www.lutron.com

Reviews: