Lutron
®
|
9
www.lutron.com
product specifications
06.28.12
369539b
Lutron
R
Comfort Controls
TouchPRO Wireless
TM
Thermostat
Wiring Guide
(for use with 24 V
~
common)
Continued on next page...
Rc
Power
R
R and Rc joined by jumper
W
Heat relay
Y
Compressor contactor
G
Fan relay
C
24 V
~
common
S1 / S2
Optional remote sensor
Rc
Power (cooling transformer)
R
Power (heating transformer)
W
Heat relay
Y
Compressor contactor
G
Fan relay
C
24 V
~
common (cooling
tranformer)
S1 / S2
Optional remote sensor
Rc
Power
R
R and Rc joined by jumper
W
Heat relay
C
24 V
~
common
S1 / S2
Optional remote sensor
Rc
Power
R
R and Rc joined by jumper
W
Heat relay
G
Fan relay
C
24 V
~
common
S1 / S2
Optional remote sensor
Rc
R and Rc joined by jumper
R
Series 20 valve terminal “R”
W
Series 20 valve terminal “B”
Y
Series 20 valve terminal “W”
C
24 V
~
common
S1 / S2
Optional remote sensor
Rc
Power
R
R and Rc joined by jumper
Y
Compressor contactor
G
Fan relay
C
24 V
~
common
S1 / S2
Optional remote sensor
Y2
Compressor contactor 2
W2
Heat 2 relay
Rc
Power
R
R and Rc joined by jumper
W
Heat relay 1
Y
Compressor contactor 1
G
Fan relay
C
24 V
~
common
S1 / S2
Optional remote sensor
Y2
Compressor contactor 2
W2
Heat relay 2
Rc
Power (cooling transformer)
R
Power (heating transformer)
W
Heat relay 1
S1 / S2
Optional remote sensor
Y
Compressor contactor 1
G
Fan relay
C
24 V
~
common (cooling
tranformer)
Conventional Systems
1H/1C System (1 transformer)
1H/1C System (2 transformers)
Heat Only System
Heat Only System With Fan
Heat Only System (Series 20)
Cool Only System
2H/2C System (1 transformer)
2H/2C System (2 transformers)