GB
45
1.2.1 Electrical data
Input:
U
=
220 - 240 V ~
(ST3)
I
max
=
8 A
cos
ϕ
>
0.7
P
max
=
1760-1920 W
Outputs:
Output 1 (Pump):
U
=
220 - 240 V ~
(ST4 and ST5)
I
max
=
4 A
cos
ϕ
>
0.7
P
max
=
880 - 960 W
Output 2 (Valve):
U
=
220 - 240 V ~
(ST4 and ST5)
I
max
=
0.5 A
cos
ϕ
>
0.7
P
max
=
77 - 84 W
Output intrinsic safety
U
=
6.6 V =
(ST1 or ST2)
I
=
165 mA
P
=
272 mW
Max. admissible outer
values for:
L (mH)
C (mF)
2
1
1
1.6
0.5
2.2
0.2
3
0.1
3.8
D. Relay module RM1/RM3 and mains unit NG1
Summary of Contents for 0212-100
Page 2: ...GB 2 ...
Page 62: ...62 GB ...
Page 65: ...65 GB ...
Page 67: ...67 GB ...
Page 69: ...69 GB Relaismodul see spare part list flow meter programm accessories ...
Page 71: ...71 GB Relaismodul see spare part list flow meter programm accessories ...