4.1 dEsign

The electrical nominal values are within a range of ± 3 

percent of the stated values of I

sc

, U

oc

 and P

max

 under 

standard test conditions (radiation density of 1,000 

W/m², AM 1.5 spectrums and a cell temperature of 

25 °C) in the sense of the tolerances of the measuring 

instruments used. 

In normal outdoor use conditions, the current strength 

and voltage produced by the module deviate from the 

values stated on the datasheet. The datasheet values 

are the values achieved under standard test condi-

tions. The short circuit current values and the open 

circuit voltage values should be correspondingly multi-

plied by a factor of 1.25 during system design in order 

to be able to sufficiently size the component voltage, 

current load capacity of the conductors, size of the 

fuses and size of the regulating devices connected to 

the modules or to the system output. 

The open circuit voltage of the PV system must not 

exceed the maximum permissible input voltage of the 

inverter used and the maximum system voltage acc. 

to the module datasheet (1,000 V). The maximum 

system voltage of other system components must also 

be observed.

Do not use modules with different configurations in 

the same system. 

Highest number of modules (N) = U

max

 system /

[U

oc

 (with STC)]

The cross-sectional area of the cable and the con-

nection capacity must correspond with the highest 

short circuit current of the system (the recommended 

cross-sectional area of the cable is 4 mm² for a single 

module, nominal current of a connection > 10 A), as 

otherwise the cable and the connection over heat at 

high current strength. 

The modules fulfil the requirements of application 

class A (IEC 61730), protection class II.

ElECtriCal  
installation

Summary of Contents for eco line 60/225-235W

Page 1: ...ECo line Modules correctly mounted...

Page 2: ...Table of contents...

Page 3: ...3 20 Information regarding this manual Safety instructions Mechanical installation Electrical installation Troubleshooting maintenance 04 06 07 08 09 13 14 16 17 19...

Page 4: ...stood prior to installation In case of any questions please contact our sales department for further explanations During installation of the module the installer must adhere to all safety precautions...

Page 5: ...her third party rights resulting from the use of the PV product A license under a patent or patent rights shall not be granted neither by implication nor by any other way The information in these inst...

Page 6: ...local grid operators Regional building regulations 1 8 Product identification Each module has labels on the back containing the following information Identification label describes the product type r...

Page 7: ...the total current strength corresponds with the total of the current strengths of the individual modules Even contact with a direct current voltage Safety instructions of 30 volts or higher is potenti...

Page 8: ...entrate the sunlight onto the modules Do not expose the rear film to direct sunlight Do not use the module near equipment or in places where flammable gases are generated or may accumulate Do not dril...

Page 9: ...s should be orientated towards the south and vice versa You will find detailed information about the best angle of inclination for installation in specialised literature or from an experienced solar i...

Page 10: ...entilation hole d 7 mm C 8 x mounting hole d 7 mm D 2 x earthing d 2 mm 3 2 Dimensional module drawings Rear front side view Eco Line 60 240 250 W Tolerance L W 3 mm H the dimensions in the order conf...

Page 11: ...8 x ventilation hole d 7 mm C 8 x mounting hole d 7 mm3 D 2 x earthing d 2 mm A B C D 808 1000 A 4 x drainage 10 10 mm B 16 x ventilation hole 3 7 mm C 8 x mounting hole 14 9 mm3 D 2 x earthing d 2 mm...

Page 12: ...llowing drawing for detailed information Load calculations are per formed by the system designer or installer Depending on the assembly rack the modules can be fastened to the assembly rack by means o...

Page 13: ...e must be properly sealed to prevent the roof from leaking Caution Danger of material damage Only use the existing mounting holes in the module frame see dimensional drawing Do not carry out any indep...

Page 14: ...the conductors size of the fuses and size of the regulating devices connected to the modules or to the system output The open circuit voltage of the PV system must not exceed the maximum permissible i...

Page 15: ...ameters of the modules are also stated on the module type plate 4 2 Earthing Caution Danger of material damage Please observe the local regulations and provision for earthing Caution Danger of materia...

Page 16: ...ircuit voltage Check the open circuit voltage of each strand with a digital multimeter The measured values should corre spond with the total of the open circuit voltage for the individual modules You...

Page 17: ...module caused by a temperature increase of the solar cells or lower radia tion density 5 1 Block diodes and bypass diodes Caution Danger of electric shock Please observe the safety instructions for w...

Page 18: ...bypass diodes If the radiation density is not very low and the volt age between the terminals deviates by more than 5 then it is probable that the port is defective 5 3 Maintenance Caution Danger of e...

Page 19: ...high priority topic for Luxor This is why modules for disposal can be returned to Luxor for recycling Submission of the delivery note or invoice stating the date of purchase is required when returnin...

Page 20: ...49 711 88 888 999 F 49 711 88 888 911 info luxor solar com www luxor solar com Printed on Recystar Polar a recycling paper with FSC certificate and the Blue Angel eco label klimaneutral gedruckt Zert...

Reviews: