background image

3

AC Input/Output Wiring Instructions

NOTE:    The  CEPS-A  can  be  field-wired  in  3  distinct  modes  of  operation.  See  “WIRING  MODES”  i n s e r t
sheet  for further details.

#1) (FACTORY DEFAULT) NORMALLY-ON:  The emergency lights connected to the CEPS-A will be ON at all
times, during both normal condition and power interruptions.  This mode is set by connecting the #1 wire on the 
red transfer switch to the utility input hot.

#2) NORMALLY-OFF:  The emergency lights connected to the CEPS-A will be OFF until a power interruption, at 
which time they will turn ON.  This mode is set by capping off the #1 wire on the red transfer switch.

#3)  NORMALLY-SWITCHED:    The  emergency  lights  connected  to  the  CEPS-A  can  be  switched  ON/OFF 
normally, until a power interruption, at which time they will turn ON regardless of switch position.  This mode is 
set by connecting the load side of a switch, time clock, or relay panel to the #1 wire on the red transfer switch.  
Please note:  Only one switch can be used per inverter.  If multiple switches are needed, wire inverter as 
NORMALLY-ON, and use LVS EPC relays.  With EPC relays an unlimited number of switch legs may be used.
Contact tech support for further details 1-800-982-4587.

The CEPS must be installed by a qualified electrician in accordance with local, state, and NEC codes.  AC & DC 
Voltages are hazardous and care should be taken to follow all instructions.  Prior to wiring AC connections, discon-

nect AC Input feed at relevant branch circuit breaker(s) and verify using proper voltage meter.  

Always wear appropriate clothing when handling batteries and equipment, and use insulated tools.

1)  Check that all input breakers are disconnected.  Trip all output breakers using a flat screwdriver.

2)  Check that knockouts on top of panel have been removed and conduits have been installed.  

3)  Bring AC Input conductors and AC Output Conductors through the appropriate conduits.  Per  

     NEC, emergency output circuit should be installed in a dedicated conduit.  

4)  Connect AC Input conductors to wires labelled “120VAC Input” or “277VAC Input”

5)  Connect AC Output conductors to wires labelled “120VAC Output” or “277VAC Output”

(277V MODELS 1000W & Larger ONLY):  Take ACME XFR out of box and mount per instructions.  Confirm 

that it has been properly configured:  X1 should be connected with X3. X2 should be connected with X4.

Connect one of XFR A wires in panel to X1&X3 in transformer (also labeled XFR A).

Connect other XFR A wire in panel to X2&X4 in transformer (also labeled XFR A).

Connect one XFR B wire in panel to H1 wire in transformer (also labeled XFR B).

Connect other XFR B wire in panel to H5 wire in transformer (also labeled XFR B).

NOTE:  For 277V systems 1000W & Larger ONLY, the XFR B wire in the transformer which is connected to 

the White with Blue Stripe (#4) XFR B wire in panel should be grounded, because it is the neutral output of an 

isolation transformer.  See transformer grounding instruction sheet provided.

6)  Connect grounds for AC Input & AC Output to grounding wires provided. 

For systems larger than 

1000W, NEC requires a grounding electrode conductor be installed from panel to grounding electrode.

7)  Refer to battery wiring instructions.

8)  Ensure that cabinet is securely fastened to wall and that no wires are loose or disconnected.

9)  Ensure all connections & grounding have been made in workman-like & code compliant manner.

Summary of Contents for CEPS-A

Page 1: ...upiment must be performed by qualified personnel 6 The use of accessory equipment not specified or recommended by LVS Inc may cause unsafe conditions and may void the warranty 7 Use caution when servicing batteries Battery acid can cause burns to skin and eyes If acid is spilled on skin or in the eyes flush with fresh water and seek medical attention immediately 8 Make sure all connections are in ...

Page 2: ...s for six years provided that the product has been properly installed in the correct surroundings TEMPORARY STORAGE INSTRUCTIONS For temporary storage of CEPS A system and batteries prior to installation select a clean cool dry location with normal ventilation suitible for human habitation and level floors DO NOT store system or batteries in a sealed room or container Ensure that floor is cabable ...

Page 3: ... and equipment and use insulated tools 1 Check that all input breakers are disconnected Trip all output breakers using a flat screwdriver 2 Check that knockouts on top of panel have been removed and conduits have been installed 3 Bring AC Input conductors and AC Output Conductors through the appropriate conduits Per NEC emergency output circuit should be installed in a dedicated conduit 4 Connect ...

Page 4: ...ing boxes and check for enclosure and terminal damage 2 Batteries should have labels and jumper wires installed C A l l a e k a M E T O N s r e p m u j y r e t t a b o t e t a m o t s r o t c e n n o c h t i w d e d i v o r p s i s s e n r a h g n i r i w n u r e m o H 3 connections prior to battery connections 5 Follow BATTERY INSTALLATION label on inside of panel door for instructions on wiring ...

Page 5: ...e 510 352 9600 1 800 982 4587 Fax 510 352 6707 www lvscontrols com CEPS 277V Output Transformer Grounding NOTE Because the provided output transformer is isolation type it is recommended to ground the 4 Wire 277V Neutral white wire with blue stripe on the transfer switch ACME TRANSFORMER XFR B Leads XFR B Leads Ground Stud black white XFR A Leads XFR A Leads TS 1000 ...

Page 6: ...3 NORMALLY SWITCHED CONNECT 1 to the load side of your wall switch time clock or occupancy sensor DO NOT connect the light itself to the switch or sensor or you will damage the invert er The lights should be connected to 120V OUTPUT or 277V OUTPUT Leads The emergency lights connected to the CEPS A can then be switched ON OFF normally until a power interruption at which time they will turn ON regar...

Page 7: ...rred If it is equal and GFCI still strips proceed to step 4 If it is not equal there is a problem with your output neutral wiring It needs to be a dedicated neutral wire going out to your lights and cannot touch the building neutral anywhere Usually one of the emergency fixtures in the field has been incorrectly connected to a normal building neutral wire As a result some of your neutral current i...

Page 8: ...ing the switch to the middle OFF position wait 5 seconds then turn it back down ON You only need to use the reset when the three LED s shown in the left side of the picture are flashing or red Normally they should all be green If first light and last light are RED indicates low battery Measure DC voltage on battery it should be between 12 5 13 8VDC RESET Middle position is OFF Bottom position is O...

Reviews: