4
If output does not match specifications or test is not successful, consult
troubleshooting guide or call 1-800-982-4587 for technical support.
#1) While input breaker is de-energized, close the output breaker(s) mounted on front or side of panel.
#2) Turn rocker switch on blue inverter (located near receptacle) to REMOTE position
(REMOTE is the downward position of the 3 position rocker switch).
#3) Check that red LED on red transfer switch box is illuminated. Green LED should be OFF.
#4) Check that emergency lighting loads are illuminated.
#5) Wait 1 minute and ensure emergency lighting loads are still illuminated.
#6) Energize input breaker and verify that green LED on red transfer switch box is illuminated.
Red LED should turn off after ~1-2 seconds.
#7) Press and hold test button on red transfer switch box. Green LED should turn off and Red LED
and emergency lights should turn on after ~1-2 seconds.
#8) Release test button, green LED should turn on, red LED should turn off.
Allow 96 hours for batteries to fully charge before performing full discharge (90 minutes) test.
Battery Installation
1. Remove batteries from shipping boxes and check for enclosure and terminal damage.
2. Batteries should have labels and jumper wires installed.
C
A
ll
a
e
k
a
M
:
E
T
O
N
.
s
r
e
p
m
u
j
y
r
e
tt
a
b
o
t
e
t
a
m
o
t
s
r
o
t
c
e
n
n
o
c
h
ti
w
d
e
d
i
v
o
r
p
s
i
s
s
e
n
r
a
h
g
n
ir
i
w
n
u
r
e
m
o
H
.
3
connections prior to battery connections.
5. Follow “BATTERY INSTALLATION” label on inside of panel door for instructions on wiring batteries.
NOTE: All connections should be made between the same colors.
(Black to Black, Red to Red, Yellow to Yellow).
6. Complete the following battery voltage tests after all batteries are installed.
Measure DC voltage between the following terminals (- is left/black terminal, + is right/red terminal):
[ALL MODELS] Battery A (-) to Battery B(+) should measure ±22 V-28V
7. Ensure that all connections have been made in a workman-like manner, and that panel door can close. It
is suggested to keep the removable battery ropes/handles either inside or near the panel, for future use.
Start-Up Instructions
Note: Blue LED function depends on WIRING mode from page 3.
For the purpose of startup test, ignore it.
4. Check all batteries for proper color connectors:
[IMPORTANT]
TYPE “A” Batteries have BLACK jumper on LEFT terminal
YELLOW jumper on RIGHT terminal
TYPE “B” Batteries have YELLOW jumper on LEFT terminal
RED jumper on RIGHT terminal