If output does not match specifications or test is not successful, consult 

troubleshooting guide or call 1-800-982-4587 for technical support.

#1)  While input breaker is de-energized, close the output breaker(s) mounted on front or side of panel.
#2)  Turn rocker switch on blue inverter (located near receptacle) to REMOTE position 

       (REMOTE is the downward position of the 3 position rocker switch).
#3)  Check that red LED on red transfer switch box is illuminated.  Green LED should be OFF.
#4)  Check that emergency lighting loads are illuminated.

#5)  Wait 1 minute and ensure emergency lighting loads are still illuminated.
#6)  Energize input breaker and verify that green LED on red transfer switch box is illuminated.  

Red LED should turn off after ~1-2 seconds.
#7)  Press and hold test button on red transfer switch box.  Green LED should turn off and Red LED

 and emergency lights should turn on after ~1-2 seconds.
#8)  Release test button, green LED should turn on, red LED should turn off.  
Allow 96 hours for batteries to fully charge before performing full discharge (90 minutes) test.

Battery Installation

1.  Remove batteries from shipping boxes and check for enclosure and terminal damage.

2.  Batteries should have labels and jumper wires installed.

 

C

A

 

ll

a

 

e

k

a

M

  

:

E

T

O

N

  

.

s

r

e

p

m

u

y

r

e

tt

a

b

 

o

e

t

a

m

 

o

s

r

o

t

c

e

n

n

o

c

 

h

ti

w

 

d

e

d

i

v

o

r

p

 

s

s

s

e

n

r

a

h

 

g

n

ir

i

w

 

n

u

e

m

o

H

  

.

3

connections prior to battery connections.

5.  Follow “BATTERY INSTALLATION” label on inside of panel door for instructions on wiring batteries.

NOTE:  All connections should be made between the same colors.

(Black to Black, Red to Red, Yellow to Yellow).

6.  Complete the following battery voltage tests after all batteries are installed.  

     Measure DC voltage between the following terminals (- is left/black terminal, + is right/red terminal):

[ALL MODELS]        Battery A (-) to  Battery B(+)  should measure ±22 V-28V

7.  Ensure that all connections have been made in a workman-like manner, and that panel door can close.  It 

is suggested to keep the removable battery ropes/handles either inside or near the panel, for future use.

Start-Up Instructions

Note: Blue LED function depends on WIRING mode from page 3.  

For the purpose of startup test, ignore it.

4.  Check all batteries for proper color connectors:

[IMPORTANT]

TYPE “A” Batteries have BLACK jumper on LEFT terminal

                                           YELLOW jumper on RIGHT terminal
TYPE “B” Batteries have YELLOW jumper on LEFT terminal 

                                           RED jumper on RIGHT terminal

Summary of Contents for CEPS-A

Page 1: ...upiment must be performed by qualified personnel 6 The use of accessory equipment not specified or recommended by LVS Inc may cause unsafe conditions and may void the warranty 7 Use caution when servicing batteries Battery acid can cause burns to skin and eyes If acid is spilled on skin or in the eyes flush with fresh water and seek medical attention immediately 8 Make sure all connections are in ...

Page 2: ...s for six years provided that the product has been properly installed in the correct surroundings TEMPORARY STORAGE INSTRUCTIONS For temporary storage of CEPS A system and batteries prior to installation select a clean cool dry location with normal ventilation suitible for human habitation and level floors DO NOT store system or batteries in a sealed room or container Ensure that floor is cabable ...

Page 3: ... and equipment and use insulated tools 1 Check that all input breakers are disconnected Trip all output breakers using a flat screwdriver 2 Check that knockouts on top of panel have been removed and conduits have been installed 3 Bring AC Input conductors and AC Output Conductors through the appropriate conduits Per NEC emergency output circuit should be installed in a dedicated conduit 4 Connect ...

Page 4: ...ing boxes and check for enclosure and terminal damage 2 Batteries should have labels and jumper wires installed C A l l a e k a M E T O N s r e p m u j y r e t t a b o t e t a m o t s r o t c e n n o c h t i w d e d i v o r p s i s s e n r a h g n i r i w n u r e m o H 3 connections prior to battery connections 5 Follow BATTERY INSTALLATION label on inside of panel door for instructions on wiring ...

Page 5: ...e 510 352 9600 1 800 982 4587 Fax 510 352 6707 www lvscontrols com CEPS 277V Output Transformer Grounding NOTE Because the provided output transformer is isolation type it is recommended to ground the 4 Wire 277V Neutral white wire with blue stripe on the transfer switch ACME TRANSFORMER XFR B Leads XFR B Leads Ground Stud black white XFR A Leads XFR A Leads TS 1000 ...

Page 6: ...3 NORMALLY SWITCHED CONNECT 1 to the load side of your wall switch time clock or occupancy sensor DO NOT connect the light itself to the switch or sensor or you will damage the invert er The lights should be connected to 120V OUTPUT or 277V OUTPUT Leads The emergency lights connected to the CEPS A can then be switched ON OFF normally until a power interruption at which time they will turn ON regar...

Page 7: ...rred If it is equal and GFCI still strips proceed to step 4 If it is not equal there is a problem with your output neutral wiring It needs to be a dedicated neutral wire going out to your lights and cannot touch the building neutral anywhere Usually one of the emergency fixtures in the field has been incorrectly connected to a normal building neutral wire As a result some of your neutral current i...

Page 8: ...ing the switch to the middle OFF position wait 5 seconds then turn it back down ON You only need to use the reset when the three LED s shown in the left side of the picture are flashing or red Normally they should all be green If first light and last light are RED indicates low battery Measure DC voltage on battery it should be between 12 5 13 8VDC RESET Middle position is OFF Bottom position is O...

Reviews: