Slim Fixture Mount Installation

2

Application

In the past, all emergency lights were left on 24 hours a day to meet safety codes.  Now  you  can 
specify  &  install  a 

UL924  Listed Emergency  Shunt Relay LUT-SHUNT-FM, 

which converts a 

normal light fixture into an approved emergency light.  During normal operation, the LUT-SHUNT-FM 
switches designated  emergency  light on and off.    During  a  utility  power  interruption,  the 
LUT-SHUNT-FM turns designated emergency light on, regardless of switch position.

Intended for use with switching and line voltage dimming controls.

What is the difference between a

SHUNT and an ALCR?

An emergency shunt relay requires a dedicated switch/dimmer to control the emergency 

lights.  In other words, the switch/dimmer must be wired on the emergency power circuit.

An automatic load control relay allows the same switch/dimmer to control both normal and 

emergency lights.  In other words, the switch/dimmer can be wired on the normal power 

circuit.

Summary of Contents for LUT-SHUNT-FM

Page 1: ... This product can be used with LED ballast tungsten and general use loads 2 Make sure all connections are in accordance with the National Electrical Code and local regulations 3 To reduce the risk of electric shock disconnect both normal and emergency power supplies before servicing 4 This product is intended to be used to control indoor and outdoor located loads 5 An unswitched AC power source is...

Page 2: ...d emergency light on and off During a utility power interruption the LUT SHUNT FM turns designated emergency light on regardless of switch position Intended for use with switching and line voltage dimming controls What is the difference between a SHUNT and an ALCR An emergency shunt relay requires a dedicated switch dimmer to control the emergency lights In other words the switch dimmer must be wi...

Page 3: ...hat the wires are connected correctly without any inconvenience to occupants do not turn off regular utility power off until you have checked each device as follows 1 Check that regular branch circuit breaker is connected utility power is available Green LED should be lit If green LED is not lit check connections continuity to branch circuit breaker 2 Check that emergency branch circuit breaker is...

Page 4: ... such as Philips SR XI040C110V054VPT1 and XI075C200V054VPT1 and Osram Dexal tm OTi50 120 277 1A4 DX L and OTi30 120 277 1A0 DX L 3 BROWN TEST UTILITY POWER 5 YELLOW 4 BLUE EMERGENCY PANEL OR INVERTER EMERGENCY NEUTRAL EMERGENCY LIGHT EMERGENCY HOT NORMAL UTILITY PANEL NORMAL NEUTRAL NORMAL HOT 20A 20A 2 WHITE 1 BLACK Lutron Vive Integral Fixture Control CAP OFF Wiring Diagram 3 For use with Lutron...

Reviews: