background image

4

Wiring Diagram #1: 

A dedicated switch or line voltage dimmer controls emergency lighting in a 

space.  Upon loss of normal power, the  emergency lighting comes on at full brightness regardless of switch 

or dimmer position.  NOTE: LUT-SHUNT-FM is not for use with 0-10V DIMMER.  Use LUT-SHUNT-D-FM.

#3 BROWN

TEST

UTILITY

POWER

#5 YELLOW

#4

BLUE

EMERGENCY 

PANEL 

OR 

INVERTER

EMERGENCY 
NEUTRAL

EMERGENCY LIGHT

EMERGENCY 
HOT

NORMAL

(UTILITY)

PANEL

NORMAL 

NEUTRAL

NORMAL 

HOT

20A

20A

#2 WHITE

#1 BLACK

SWITCH

OR DIMMER

(CAP OFF)

Can I power more than 1 light from the LUT-SHUNT-FM?

It is recommended that the LUT-SHUNT-FM power only one fixture/luminaire.  
If you want to control more than one fixture/luminaire, use the higher rated LUT-SHUNT.

Wiring Diagram #2: 

For use with Lutron Vive integral fixture controls and DALI drivers 

with self powered DALI link, such as Philips® SR XI040C110V054VPT1 and XI075C200V054VPT1

and Osram ® Dexal (tm) OTi50/120-277/1A4 DX L and OTi30/120-277/1A0 DX L

#3 BROWN

TEST

UTILITY

POWER

#5 YELLOW

#4

BLUE

EMERGENCY 

PANEL 

OR 

INVERTER

EMERGENCY 
NEUTRAL

EMERGENCY LIGHT

EMERGENCY 
HOT

NORMAL

(UTILITY)

PANEL

NORMAL 

NEUTRAL

NORMAL 

HOT

20A

20A

#2 WHITE

#1 BLACK

Lutron 

Vive Integral 

Fixture Control

(CAP OFF)

Wiring Diagram #3: 

For use with Lutron Vive integral fixture controls and EcoSystem drivers 

without self powered DALI link, such as Lutron LDE1, LDE5,  L3D, and L3D0

LINE

NEUTRAL

A

B

#3 BROWN

TEST

UTILITY

POWER

#5 YELLOW

#4

BLUE

EMERGENCY 

PANEL 

OR 

INVERTER

EMERGENCY 
NEUTRAL

EMERGENCY LIGHT

EMERGENCY 
HOT

NORMAL

(UTILITY)

PANEL

NORMAL 

NEUTRAL

NORMAL 

HOT

20A

20A

#2 WHITE

#1 BLACK

(CAP OFF)

LINE

NEUTRAL

E1

E2

Lutron

Fixture Control 

Digital Interface

E1

E2

Blue Wires

(polarity independent)

Philips® SR:                  A = SR+         B = SR-

Osram ® Dexal:          A = DEXAL+ B = DEXAL-

Violet Wires

(polarity independent)

S+

S-

Blue 

Wires

(polarity 

independent)

Lutron 

Vive 

Integral 

Fixture 

Control

L

N

EMERGENCY HOT
EMERGENCY NEUTRAL

Summary of Contents for LUT-SHUNT-FM

Page 1: ... This product can be used with LED ballast tungsten and general use loads 2 Make sure all connections are in accordance with the National Electrical Code and local regulations 3 To reduce the risk of electric shock disconnect both normal and emergency power supplies before servicing 4 This product is intended to be used to control indoor and outdoor located loads 5 An unswitched AC power source is...

Page 2: ...d emergency light on and off During a utility power interruption the LUT SHUNT FM turns designated emergency light on regardless of switch position Intended for use with switching and line voltage dimming controls What is the difference between a SHUNT and an ALCR An emergency shunt relay requires a dedicated switch dimmer to control the emergency lights In other words the switch dimmer must be wi...

Page 3: ...hat the wires are connected correctly without any inconvenience to occupants do not turn off regular utility power off until you have checked each device as follows 1 Check that regular branch circuit breaker is connected utility power is available Green LED should be lit If green LED is not lit check connections continuity to branch circuit breaker 2 Check that emergency branch circuit breaker is...

Page 4: ... such as Philips SR XI040C110V054VPT1 and XI075C200V054VPT1 and Osram Dexal tm OTi50 120 277 1A4 DX L and OTi30 120 277 1A0 DX L 3 BROWN TEST UTILITY POWER 5 YELLOW 4 BLUE EMERGENCY PANEL OR INVERTER EMERGENCY NEUTRAL EMERGENCY LIGHT EMERGENCY HOT NORMAL UTILITY PANEL NORMAL NEUTRAL NORMAL HOT 20A 20A 2 WHITE 1 BLACK Lutron Vive Integral Fixture Control CAP OFF Wiring Diagram 3 For use with Lutron...