4
Wiring Diagram #1:
A dedicated switch or line voltage dimmer controls emergency lighting in a
space. Upon loss of normal power, the emergency lighting comes on at full brightness regardless of switch
or dimmer position. NOTE: LUT-SHUNT-FM is not for use with 0-10V DIMMER. Use LUT-SHUNT-D-FM.
#3 BROWN
TEST
UTILITY
POWER
#5 YELLOW
#4
BLUE
EMERGENCY
PANEL
OR
INVERTER
EMERGENCY
NEUTRAL
EMERGENCY LIGHT
EMERGENCY
HOT
NORMAL
(UTILITY)
PANEL
NORMAL
NEUTRAL
NORMAL
HOT
20A
20A
#2 WHITE
#1 BLACK
SWITCH
OR DIMMER
(CAP OFF)
Can I power more than 1 light from the LUT-SHUNT-FM?
It is recommended that the LUT-SHUNT-FM power only one fixture/luminaire.
If you want to control more than one fixture/luminaire, use the higher rated LUT-SHUNT.
Wiring Diagram #2:
For use with Lutron Vive integral fixture controls and DALI drivers
with self powered DALI link, such as Philips® SR XI040C110V054VPT1 and XI075C200V054VPT1
and Osram ® Dexal (tm) OTi50/120-277/1A4 DX L and OTi30/120-277/1A0 DX L
#3 BROWN
TEST
UTILITY
POWER
#5 YELLOW
#4
BLUE
EMERGENCY
PANEL
OR
INVERTER
EMERGENCY
NEUTRAL
EMERGENCY LIGHT
EMERGENCY
HOT
NORMAL
(UTILITY)
PANEL
NORMAL
NEUTRAL
NORMAL
HOT
20A
20A
#2 WHITE
#1 BLACK
Lutron
Vive Integral
Fixture Control
(CAP OFF)
Wiring Diagram #3:
For use with Lutron Vive integral fixture controls and EcoSystem drivers
without self powered DALI link, such as Lutron LDE1, LDE5, L3D, and L3D0
LINE
NEUTRAL
A
B
#3 BROWN
TEST
UTILITY
POWER
#5 YELLOW
#4
BLUE
EMERGENCY
PANEL
OR
INVERTER
EMERGENCY
NEUTRAL
EMERGENCY LIGHT
EMERGENCY
HOT
NORMAL
(UTILITY)
PANEL
NORMAL
NEUTRAL
NORMAL
HOT
20A
20A
#2 WHITE
#1 BLACK
(CAP OFF)
LINE
NEUTRAL
E1
E2
Lutron
Fixture Control
Digital Interface
E1
E2
Blue Wires
(polarity independent)
Philips® SR: A = SR+ B = SR-
Osram ® Dexal: A = DEXAL+ B = DEXAL-
Violet Wires
(polarity independent)
S+
S-
Blue
Wires
(polarity
independent)
Lutron
Vive
Integral
Fixture
Control
L
N
EMERGENCY HOT
EMERGENCY NEUTRAL