6. Select the position of the relay in the zone. This
set the order in which they turn on and off. Or
in the case of DMX or sACN, the address order.
(Figure 5-11). Note: DMX and sACN zones default
to individual addressing. If you choose “All
Available” the entire panel or panels will change
to DMX or sACN.
7. For sequenced operation, select a delay time from
the dropdown. Relays in grouped zones toggle
in 25ms intervals. (Figure 5-11) Delay time is
the amount of time after a relay changes state,
before the new relay in sequence changes state.
If using one of the custom delay settings, enter
the desired delay time in the custom delay setting
fi eld. (Figure 5-12)
Figure 5-11
Click the up/down
arrows to change
the relay’s position/
address in the zone.
Select a delay time for
the relay.