lynxspring.com
shop.lynxspring.com
1210 NE Windsor Drive
Lee’s Summit, MO 64086
sales@lynxspring.com
1 (877) 649-5969
© 2017 Lynxspring, Inc.
All Rights Reserved
Revised 2/21/2017
Page
15
of
16
BACnet/IP Communication Set-Up on External JENEsys Device
161.75.85.62 in the example below is the IP Address of the JENEsys Ethernet Port
If Router is on the Private Network, a VPN connection is required
In this case, the Adapter selected should be the virtual adapter created by the
VPN connection
(In Windows, this is called a TAP Adapter)
Figure 12
Note:
The internal JENEsys Device Comm Setup is typical – no special configuration needed
Connecting a JENE to the Cellular Router (BACnet/IP)
Make sure the Device Name, Device ID, and Device Network match the BACnet device. Enter the MAC address
as the Public IP address with BACnet Port
(example 161.75.85.62:0xBAC0)
Figure 10