5.9
P0(IPM malfunction or IGBT over-strong current protection diagnosis and solution)
Description:
When the
voltage signal the IPM sends to the compressor drive chip is abnormal, the display LED shows
“P0” and the AC turn off.
Recommended parts to prepare:
• Wiring mistake
• IPM malfunction
• Faulty outdoor fan assembly
• Compressor malfunction
• Faulty outdoor PCB
Troubleshooting and repair:
Check the wiring
between
PCB and compressor.
Does an error exist?
YES
Ensure proper connections or
replace the wires and connectors.
NO
Check the IPM.
Is it in working order?
NO
Replace the IPM board or
replace the outdoor PCB.
YES
Check the outdoor fan and
the
outdoor unit
ventilation.
Is it in working order?
Please refer to the solution of the
“
Fan
NO
Speed is Out of Control
”
malfunction.
YES
Check the compressor
resistance values.
Are they
within
acceptable parameters?
NO
Replace the compressor.
YES
Replace the outdoor PCB.