background image

WIRING INSTRUCTIONS

 

SCREW TERMINAL 

Torque: 0.8 N·m

JUMPER SETTINGS

4 kΩ is attached for open collector and mechanical contact 
input, while 200 Ω, 510 Ω or 1 kΩ is attached for two-wire 
current pulse input. 
Resistance can be changed by modifying jumper combina-
tions as shown in the table below.

Jumper settings

INPUT

J1

J2

J3

J4

J5

J6

1: Mechanical contact

2 - 3 2 - 3 2 - 3 1 - 2 1 - 2 1 - 2*

2: Open collector

2 - 3 2 - 3 2 - 3 1 - 2 1 - 2 2 - 3

3: Voltage pulse

2 - 3 2 - 3 2 - 3 2 - 3 2 - 3 2 - 3

4:   Two-wire  current 

pulse (200 Ω)

1 - 2 2 - 3 2 - 3 2 - 3 2 - 3 2 - 3

5:   Two-wire  current 

pulse (510 Ω)

2 - 3 1 - 2 2 - 3 2 - 3 2 - 3 2 - 3

6:   Two-wire  current 

pulse (1 kΩ)

2 - 3 2 - 3 1 - 2 2 - 3 2 - 3 2 - 3

* Close 2 - 3 for turning the filter off.

CHECKING

1) Terminal wiring:  Check that all cables are correctly con-

nected according to the connection diagram.

2) Power input voltage:  Check voltage supplied to the rack 

(model: 18BXx or 18KBXx).  For the DC power source, be 

sure that the ripple level is within 10% p-p.

3) Input:  For the mechanical contact input, check that the 

input frequency is 5 Hz or less and the pulse width is 20 

msec. or more.

  For the open collector input, check that the input fre-

quency is 10 kHz or less and the pulse width is 20 μsec. 

or more.

  For the voltage pulse input or two-wire current pulse in-

put, be sure that the input signal is as shown in the table 

below. 

• Waveform requirements

Square Waveform

FREQUENCY RANGE AMPLITUDE PULSE WIDTH & DUTY RATIO

0 to 10 kHz

1 to 3V p-p

Duty 50 ±10%

0 to 10 kHz

Min. 3V p-p

Min. 60 μsec.*

*  When the frequency is 6 kHz or more, the pulse width is 30 

μsec. or more.

Sine or similar waveform

FREQUENCY RANGE AMPLITUDE PULSE WIDTH & DUTY RATIO

50 Hz to 10 kHz

1 to 3V p-p

10 Hz to 10 kHz

Min. 3V p-p

4) Output:  Check that the output voltage is 0 V at ON, 30 V 

DC or less at OFF.

  Check also that the output current is 100 mA or less at 

ON, 0 mA at OFF.

LIGHTNING SURGE PROTECTION

M-System offers a series of lightning surge protector for 
protection against induced lightning surges.  Please contact 
M-System to choose appropriate models.

18PP

5-2-55, Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN
Phone: +81(6)6659-8201  Fax: +81(6)6659-8510  E-mail: info@m-system.co.jp

EM-1861  Rev.6  P. 3 / 3

Reviews: