TERMINAL CONNECTIONS
Connect the module as in the diagram below.
■
EXTERNAL DIMENSIONS unit : mm (inch)
44 (1.73) dia.
6.3
(.25)
33 (1.30)
6 (.24) dia.
16.5 (.65)
6–M3 SCREW
2–4.5 (.18) dia.
MTG HOLE
20.7 (.81)
19.5 (.77)
12.7 (.5)
1
4
3
2
–
+
7.6 (.30) dia.
■
CONNECTION DIAGRAM
4
2
3
1
+
–
LOAD
OUTPUT
24V DC
4 – 20mA DC
*
2
INPUT
*
1
*
1. Input Connection Examples
4
2
3
1
■
DC MILLIVOLT
+
–
INPUT
4
2
3
1
■
THERMOCOUPLE
• Single input
+
–
–
+
comp. leadwire
4
2
3
1
■
RTD & RESISTANCE
• Two-wire
4
2
3
1
• Three-wire
4
2
3
1
• Dual input
+
+
–
+
–
comp. leadwire
+
–
B
B
A
B
A
4
2
3
1
• Four-wire
B
B
A
A
SENSOR 2
SENSOR 1
*
2. Limited to 250 – 500Ω when using the communication
to configure the module.
WIRING INSTRUCTIONS
■
SCREW TERMINAL
Torque: 0.5 N·m
CHECKING
1) Terminal wiring: Check that all cables are correctly con-
nected according to the connection diagram.
2) Input: Check that the input signal is within 0 – 100% of
full-scale.
If the thermocouple / RTD or its extension wires are bro-
ken, the output goes over 100% (below 0% with down-
scale) due to the burnout function. Check leadwires in
such a case.
3) Output: Check that the load is within the permissible
limit including wiring resistance.
Load Resistance (Ω) =
Supply Voltage (V) – 9 (V)
0.023 (A)
(including leadwire resistance)
ADJUSTMENT PROCEDURE
To calibrate the signal to match with a receiving instru-
ment or to change the factory-set configurations, use the PC
Configurator software installed on a Windows PC via the
Bell202 Modem (model COP-HU).
The PC Configurator software is downloadable at M-Sys-
tem’s web site: http://www.m-system.co.jp
LIGHTNING SURGE PROTECTION
M-System offers a series of lightning surge protector for
protection against induced lightning surges. Please contact
M-System to choose appropriate models.