3. POINTS OF CAUTION
■
POWER INPUT RATING & OPERATIONAL RANGE
• Locate the power input rating marked on the product and confirm its operational range as indicated below:
85 – 132V AC rating
:
85 – 132V, 47 – 66 Hz, approx. 4VA
24V DC rating
:
24V ±10%, approx. 4W
■
GENERAL PRECAUTIONS
• Before you remove the unit from its base socket or mount it, turn off the power supply, input signal and output signal for
safety.
■
ENVIRONMENT
• Indoor use.
• When heavy dust or metal particles are present in the air, install the unit inside proper housing with sufficient ventilation.
• Do not install the unit where it is subjected to continuous vibration. Do not subject the unit to physical impact.
• Environmental temperature must be within -5 to +55°C (23 to 131°F) with relative humidity within 30 to 90% RH in order
to ensure adequate life span and operation.
■
WIRING
• Do not install cables close to noise sources (relay drive cable, high frequency line, etc.).
• Do not bind these cables together with those in which noises are present. Do not install them in the same duct.
■
AND ....
• The unit is designed to function as soon as power is supplied, however, a warm up for 10 minutes is required for satisfying
complete performance described in the data sheet.
60C
5-2-55, Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN
Phone: +81(6)6659-8201 Fax: +81(6)6659-8510 E-mail: info@m-system.co.jp
EM-6602 Rev.8 P. 3 / 13