AD2LC

P. 2 / 5

EM-1388 Rev.2

FRONT PANEL CONFIGURATION & PROGRAMMING

 PROGRAMMING PROCEDURE

1) Press ITEM UP or DOWN key until ITEM display indicates “01”.
2) Press DATA UP or DOWN key and choose “2” on DATA display.

1  : Data indication only.
2  : All parameters are modifiable.

3) Press ITEM UP or DOWN key until ITEM display shows the ITEM No.

you need to change.

4) Press DATA UP or DOWN key and choose a DATA No. or value you need

on Data display.

5) Repeat above 3 and 4.  (Entered data is stored 1 sec. after the operation

has been complete.)

6) Press ITEM UP or DOWN key until ITEM display indicates “01”.
7) Press DATA UP or DOWN key and choose “1” on the display.
8) Press ITEM UP or DOWN key until ITEM display indicates “P”.  DATA

display shows process input.  You can now check data setting by choosing ITEM No.

Note : DO NOT press UP and DOWN keys simultaneously.

DATA

ITEM

DATA

ITEM

ITEM
UP-DOWN Keys

PL2 (HOLD) LED

PL1 (POL) LED

DATA Display

ITEM Display

DATA
UP-DOWN Keys

26-pin Connector

(Pin Assignments)

1

2

25

26

MDF.

CODE

ITEM

DATA

CONTENTS

DEFAULT

P

N/A

-9999 – 9999

Output display in engineering unit, BCD (as set in ITEM 17/18)

––

(-FFFF – FFFF)

(  ) for binary, offset binary, two's complement, reflected binary

01

1, 2

Modification code

1 : Data indication only.

1

2 : All parameters are modifiable.

02

N/A

0 – 99

Status indication (“0” is normally indicated.)

––

03

N/A

0, 1, 2

Input range code

0 : S1 (0.0 –   3.0mV/V)

User specified

1 : S2 (0.0 – 10.0mV/V)
2 : S3 (0.0 – 30.0mV/V)

04

2

0.1 – 12.0

Excitation voltage (V)

1.0V

05

2

0.010 – 3.000

Sensor sensitivity

S1 : 0.0 –   3.0mV/V

  3.000

0.010 – 9.999

S2 : 0.0 – 10.0mV/V

  9.999

0.10 – 30.0

S3 : 0.0 – 30.0mV/V

30.00

Used when adjusting the sensor sensitivity by its rating value.
Set ITEM 06 before 05.

06

2

-30.00 – 30.00

0% input voltage

S1 : -30.00 – 30.00mV

-99.99 – 99.99

S2 : -99.99 – 99.99mV

-300.0 – 300.0

S3 : -300.0 – 300.0mV

Sensor's zero adjustment.  Approximate offset voltage.

07

2

-30.00 – 30.00

100% input voltage

S1 : -30.00 – 30.00mV

-99.99 – 99.99

S2 : -99.99 – 99.99mV

-300.0 – 300.0

S3 : -300.0 – 300.0mV

Used when adjusting the sensor sensitivity with an actual load.
Set ITEM 06 before 07.

08

2

10.0 – 100.0

Load ratio (%)

100.0

Used when adjusting the sensor sensitivity with an actual load.

09

2

-999.9 – 999.9

Tare adjustment (%)

0.0

10

N/A

-15.0 – 115.0

Input indicated in % (of the range set in ITEM 05/06/07)

––

11

2

-99.99 – 99.99

Zero adjustment (%) (fine adj. of the value set in ITEM 05/06/07)

0.00

12

2

0.000 – 9.999

Gain adjustment (fine adj. of the value set in ITEM 05/06/07)

1.000

13

2

0, 1, 2, 3, 4

Moving average (200 msec./sampling)

0

0: No      1: 4 samples      2: 8 samples      3: 16 samples      4: 32 samples

14

2

0, 1, 2, 3

Contact input function

0 : Tare adjustment

0

1 : Peak hold
2 : Valley hold
3 : Sample hold

15

2

10 – 99

Power ON-delay time (seconds)

10

16

2

0, 1 – 60

Power-saving mode

0 : Continuous display

10

1 – 60 : Time before display turned off (minutes)