background image

B3FR

P. 4 / 4

EM-7514 Rev.6

5-2-55, Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN
Phone: +81(6)6659-8201   Fax: +81(6)6659-8510   E-mail: info@m-system.co.jp

ADJUSTMENT PROCEDURE

This unit is calibrated at the factory to meet the ordered 
specifications, therefore you usually do not need any cali-
bration.

For matching the signal to a receiving instrument or in case 
of regular calibration, adjust the output as explained in the 

following.

 HOW TO CALIBRATE THE OUTPUT SIGNAL

Use a signal source and measuring instruments of sufficient 
accuracy level.  Turn the power supply on and warm up for 

more than 10 minutes.
1)  ZERO:  Apply 0% input and adjust output to 0%.
2)  SPAN:  Apply 100% input and adjust output to 100%.
3)  Check ZERO adjustment again with 0% input.
4)  When  ZERO  value  is  changed,  repeat  the  above  proce

-

dure 1) – 3).

MAINTENANCE

Regular calibration procedure is explained below:

 CALIBRATION

Warm up the unit for at least 10 minutes.  Apply 0%, 25%, 
50%,  75%  and  100%  input  signal.    Check  that  the  output 

signal for the respective input signal remains within accu-

racy described in the data sheet.  When the output is out of 
tolerance,  recalibrate  the  unit  according  to  the “ADJUST

-

MENT PROCEDURE” explained earlier.

CHECKING

1)  Terminal wiring:  Check that all cables are correctly con

-

nected according to the connection diagram.

2)  DIP SW setting:  Check that the switches are set to ap

-

propriate positions.

3)  Input:  Check voltage across the terminal 4 – 5 with a 

sensitive voltmeter.

  (With 20°C or 68°F, approx. 110 mV with Pt 100, approx. 

140 mV with Ni 120, approx. 10 mV with Cu 10.)

  If the RTD or its extension wires are broken, the output 

goes  over  100%  (below  0%  with  downscale  protection) 

due to burnout function.  Check leadwires in such a case.

4)  Output:  Check that the load is within the permissible 

limit including wiring resistance.  

   

 

 

       Supply Voltage (V) – 12 (V)

  Load Resistance (Ω) = –––––––––––––––––––––––– 

   

 

 

 

         0.02 (A)

 

 

   (including 

leadwire 

resistance)

5)  When you check the output signal, connect an ammeter 

of  which  the  internal  resistance  is  of  10  Ω  max.  to  the 

monitor terminals.

EXTERNAL DIMENSIONS

  mm (inch)

10 11 12

4

5

6

106 (4.17)

18 (.71)

110.5 (4.35)

62 (2.44)

[5 (.20)]

DIN RAIL

35mm wide

• When mounting, no extra space is needed between units.

Reviews: