background image

EM-8007-L  Rev.1  P. 1 / 7

MG CO., LTD. www.mgco.jp

5-2-55 Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN

INSTRUCTION MANUAL

Devicenet

®

 I/O MODULE

(PNP discrete output, 16 points, e-CON connector)

MODEL

R7F4DD-DC16B-H

BEFORE USE ....

Thank you for choosing us.  Before use, please check con-
tents of the package you received as outlined below.
If you have any problems or questions with the product, 
please contact our sales office or representatives.

 

PACKAGE INCLUDES:

Discrete output module.......................................................(1)
DIN rail mounter slider ......................................................(2)

 

MODEL NO.

Confirm Model No. marking on the product to be exactly 
what you ordered.

 

INSTRUCTION MANUAL

This manual describes necessary points of caution when 
you use this product, including installation, connection and 
basic maintenance procedures.

 

EDS FILE

EDS files are downloadable at our web site.

POINTS OF CAUTION

 

CONFORMITY WITH EU DIRECTIVES

• The equipment must be mounted inside the instrument 

panel of a metal enclosure.

• The actual installation environments such as panel con-

figurations, connected devices, connected wires, may af-
fect the protection level of this unit when it is integrated 
in a panel system.  The user may have to review the CE 
requirements in regard to the whole system and employ 
additional protective measures* to ensure the CE con-
formity.
* For example, installation of noise filters and clamp fil-

ters for the power source, input and output connected 
to the unit, etc.

 

GENERAL PRECAUTIONS

• Before you remove the unit or mount it, turn off the power 

supply and output signal for safety.

• Before you remove the terminal block or mount it, make 

sure to turn off the power supply and output signal for 
safety.

• DO NOT set the switches on the module while the power 

is supplied. The switches are used only for maintenance 
without the power.

 

ENVIRONMENT

• Indoor use.
• When heavy dust or metal particles are present in the 

air, install the unit inside proper housing with sufficient 
ventilation.

• Do not install the unit where it is subjected to continuous 

vibration.  Do not subject the unit to physical impact.

• Environmental temperature must be within -10 to +55°C 

(14 to 131°F) with relative humidity within 30 to 90% RH 
in order to ensure adequate life span and operation.

• Observe at the minimum of 10 mm left and right the 

units for heat dissipation when mounting vertically.

 

WIRING

• Do not install cables close to noise sources (relay drive 

cable, high frequency line, etc.).

• Do not bind these cables together with those in which 

noises are present.  Do not install them in the same duct.

 

AND ....

• The unit is designed to function as soon as power is sup-

plied, however, a warm up for 10 minutes is required for 
satisfying complete performance described in the data 
sheet.

DeviceNet is registered trademark of ODVA.

Summary of Contents for Devicenet R7F4DD-DC16B-H

Page 1: ...E con formity For example installation of noise filters and clamp fil ters for the power source input and output connected to the unit etc GENERAL PRECAUTIONS Before you remove the unit or mount it tu...

Page 2: ...ED green indicators shows the signal status ON LED ON OFF LED OFF NODE ADDRESS The left switch determines the tenth place digit while the right switch does the ones place digit of the address Address...

Page 3: ...2 SNSR EXC Exc supply Input Termianal Assignment 1 4 1 4 1 4 1 4 Y0 Y1 Y2 Y3 Y4 Y5 Y6 Y7 Y8 Y9 YA YB YC YD YE YF Unit side connector 37216 62M3 004PL 3M company Cable side connector 37104 000FL 3M co...

Page 4: ...the unit from the DIN rail A C B SURFACE MOUNTING 1 Insert the two DIN rail mounter sliders until it clicks once as shown below A A 2 Mount the unit with M4 screws referring to the External Dimension...

Page 5: ...am below EXTERNAL DIMENSIONS unit mm inch 115 4 53 41 1 61 123 4 84 138 5 43 50 1 97 5 20 3 12 DIN rail 35mm wide 4 16 2 4 3 17 dia 4 16 deep CONNECTION DIAGRAM Y0 GND NC NC 1 3 4 2 SNSR EXC SNSR EXC...

Page 6: ...software model R7CFG Refer to the users manual of the software for detailed operations INTERFACE SETTING PARAMETER SETTING RANGE DEFAULT SETTING Communication Timeout 0 32767 0 1 sec 10 0 1 sec DATA...

Page 7: ...d Unused 0 Normal 1 Voltage drops Approx 16 V 0 Normal 1 Voltage drops Approx 16 V TRANSMISSION DATA DESCRIPTIONS I O DATA Unit word MODEL OUTPUT DATA 1 R7F4DD to master INPUT DATA 2 master to R7F4DD...

Reviews: