168
DL8 USERS
MANUAL EM-7691-B Rev.24
(continued from previous page)
FILE NAME
DATA
VARIABLE DEFINITION FORMAT
event_log.json
Present time
{
year:2014,
mon:7,
day:3,
hour:17,
min:0,
sec:0,
dl_time1:"2014/07/03",
dl_time2:"17:00:00",
Number of events
event_cnt:128,
(Number of array elements in the following format descriptions
equals the number of events.)
Date/Time (Year/Mon/Day)
Date/Time (Hour/Min/Sec)
CH
CH name
CH comment
Event message string
Color
ev_time1:["2014/07/03",...],
ev_time2:["11:00:00",...],
ev_ch:["AI1","AI2","AI3","AI4",...],
ev_comment:["AI1","AI2","AI3","AI4",...],
ev_comment:["AI1","AI2","AI3","AI4",...],
ev_message:["HH","L","NORMAL","H",...],
ev_color:["#008040",...]
}
16.4.4 XML FORMAT DATA FILES (command.xml)
Cloud mode : Not available (Commands are executed by the DL8 device itself.)
TAG 1
TAG 2
TAG 3
(start)
VALUE
DATA
TAG 3
(end)
NOTES
<DL_CMD>
<DO>
<CH
■
>
ON
OFF
Turn DO
■
ON
Turn DO
■
OFF
</CH
■
>
■
: 1 to 64
</DO>
<PI>
<CH
■
>
RESET
Reset PI
■
count
</CH
■
>
■
: 1 to 32
<CH
■
>
(Engineering unit value)
Preset PI
■
count
</CH
■
>
</PI>
<CI>
<CH
■
>
RESET
Reset DI
■
count
</CH
■
>
■
: 1 to 64
<CH
■
>
(Accumulated value)
Preset DI
■
count
</CH
■
>
</CI>
<AO>
<CH
■
>
(Engineering unit value)
Set AO
■
output value
</CH
■
>
■
: 1 to 32
</AO>
</DL_CMD>