47
DL8 USERS
MANUAL EM-7691-B Rev.24
7.4 PULSE INPUT (PI)
7.4.1 ASSIGNING I/O SIGNALS
A maximum of 32-point pulse inputs (PI1 to PI32) can be monitored. 32-bit integer data used for power monitoring signals
and analog accumulation value for analog input (AI) are assigned to PI.
Assign 32-bit data inputs of remote I/Os connected to the DL8, following the procedure below.
7.4.1.1 ASSIGNING I/O MODULE TO PI
(1) Click [Pulse input (PI)] button in the “Input/Output” menu to open “Pulse Input (PI)” list.
Double-click a row of the PI channel to configure to open the PI configuration dialog.
Input/Output
Pulse input (PI)
PI Configuration dialog
2.Double-click
1.Click
(2) Choose “I/O module” under “CH setting” and assign “Module address” and enter “CH No.” (Refer to 5. CONNECTING
1. Select “I/O module”
2. Enter “Module address”
and “CH No.”
1 channel of pulse input is available per module. When a 4-channel module is installed, use 4 module addresses.
(N: module address assigned to the module)
MODULE TYPE
MODEL NUMBER
CH NO.
MODULE ADDRESS OF
DL8
CH NO. OF DL8
4-channel module
R8-PA4
CH1
N
1
CH2
N+1
1
CH3
N+2
1
CH4
N+3
1
NOTE
• For pulse input, only 32 bit data is available. It is not available for the products using 16 bit data (model: R3-PA16, etc.)