7.6 ANALOG OUTPUT (AO)
7.6.1 ASSIGNING I/O SIGNALS
A maximum of 32-point analog outputs (AO1 to AO32) can be used.
Assign analog outputs of I/O modules and/or remote I/Os connected to the DL8, following the procedure below.
7.6.1.1 ASSIGNING I/O MODULE TO AO
(1) Click [Analog output (AO)] button in “Input/Output” menu to open “Analog output (AO)” list.
Double-click a row of the AO channel to configure to open the AO configuration dialog.
Input/Output
Analog output (AO)
AO Configuration dialog
2.Double-click
1.Click
(2) Choose “I/O module” under “CH setting” to assign “Module address” and enter “CH No.” (Refer to 5. CONNECTING I/O
1. Select “I/O module”
2. Enter “Module address”
and “CH No.”
2 channels of analog output are available per module. When a 4-channel module is installed, use 2 module addresses.
(N: module address assigned to the module)
MODULE TYPE
MODEL NUMBER
CH NO.
MODULE ADDRESS OF
DL8
CH NO. FOR DL8
2-channel module
R8-YS2
R8-YS2NJ
CH1
N
1
CH2
N
2
4-channel module
R8-YV4N
R8-PC4A
R8-YST4N
CH1
N
1
CH2
N
2
CH3
N+1
1
CH4
N+1
2