140
DL8 USERS
MANUAL EM-7691-B Rev.24
14. OTHER SETTINGS
14.1 CLOCK SYNCHRONIZATION
14.1.1 SNTP
The SNTP client function is used for automatic clock time correction.
The internal RTC is adjusted when the date changes (at 0 hour) and at power up.
Follow the procedure shown below to set the SNTP.
(1) Connect the DL8 with the COP-US cable to the PC to which the DLCFG is installed.
For connection setting, refer to 4.3 IP ADDRESS SETTING.
COP-US
CFG
DLCFG
(2) Start the DLCFG to show the main window.
Click [Download from device] button to read setting from the DL8 and to open “Configuration” window.
Click [Communication] button to open “Communication” menu.
Then click [SNTP] button to open “SNTP” dialog.
Main Window
1.Click
2.Click
Configuration
Communication
3.Click
SNTP
(3) See the following table and configure each parameter.
PARAMETER
DESCRIPTION
Mode
Set “Disable” or “Enable” for the SNTP client function of DL8.
Server
Set a domain name or IP address of the SNTP server to connect.
(4) Click [OK] button to temporarily save the setting.
To enable the setting, return to “Configuration” window and click [Upload to device] button.
NOTE
• To apply the new setting to the DL8, save and restart the device.
• Be sure to set time zone according to the DL8 location to use the automatic time correction function.
Refer to 14.1.2 TIME ZONE
• When Mode of SNTP is set to “Enable” and time of the DL8 is changed over the turn of a day, the clock synchroniza-
tion works.