7.2 ANALOG INPUT (AI)
7.2.1 ASSIGNING I/O SIGNALS
A maximum of 32-point analog inputs (AI1 to AI32) can be monitored.
Assign analog inputs of I/O modules and/or remote I/Os connected to the DL8, following the procedure below.
16 bit integer data can be handled. Allocate 32 bit integer data such as power data to pulse input (PI).
7.2.1.1 ASSIGNING I/O MODULE TO AI
(1) Click [Analog input (AI)] button in “Input/Output” menu to open “Analog input (AI)” list.
Double-click a row of the AI channel to configure to open the AI configuration dialog.
Input/Output
Analog input (AI)
AI Configuration dialog
2.Double-click
1.Click
(2) Choose “I/O module” under “CH setting” and assign “Module address” and enter “CH No.” (Refer to 5. CONNECTING
1. Select “I/O module”
2. Enter “Module address” and “CH No.”