7.3.3 ALARM OUTPUT (TYPE B, C, D & E)
A specific DO can be turned on or off when the input status or counter value is true to the event value.
(1) Clicking [Alarm output] button in the “DI” configuration dialog opens the “Alarm output” list. Double click a DO channel
to control ON/OFF operation.
2.Double-click
5.Click
1.Click
1.Click
1.Click
6.Click
Alarm output
DI Configuration Dialog
4.Click
3. Select OFF/ON
(2) Click [OK] button to temporarily save the setting.
NOTE
• This function is not available for Type A.
• DO setting must be finished in advance. (Refer to 7.5 DISCRETE OUTPUT (DO).)
• When alarm output turns on a DO, the ON status is maintained while input status is true.
• DO controlled by web server or Modbus/TCP server, is operated in OR logic against the alarm output.
• When alarm output is not used, set it to OFF.
7.3.4 COPYING CH CONFIGURATION
CH configuration of one channel can be copied to another. Refer to 7.2.5 COPYING CH CONFIGURATION.