7.4.6 RESETTING COUNTER IN A REGULAR INTERVAL
This function is added to the DL8 Ver. 1.5.x or later.
AI “Time” input is used to reset PI counters in a regular interval so that pulse counts for a fixed period can be logged con-
tinuously.
Refer to the following setting examples.
■
Logging pulse counts for every minute, resetting at 0 second
SETTING DIALOG
PARAMETER
DESCRIPTION
AI1
CH setting
Time
Time input
Second
Alarm zone setting
Partitions : 2
Zone 1 upper limit = Zone 2 = 10
PI Reset : Reset PI1 in Zone 1
PI1
Assign the relevant pulse input channel.
Data logging
Storing rate time unit
Minute
Storing rate (min.)
1
Channel setting
Specify PI1
■
Logging pulse counts for every hour, resetting at 0 minute
SETTING DIALOG
PARAMETER
DESCRIPTION
AI1
CH setting
Time
Time input
Minute
Alarm zone setting
Partitions : 2
Zone 1 upper limit = Zone 2 lower limit = 10
PI Reset : Reset PI1 in Zone 1
PI1
Assign the relevant pulse input channel.
Data logging
Storing rate time unit
Hour
Storing rate (hour)
Hour : Check all hours from 00 to 23.
Offset (min.) : 0 for all hours
Offset (sec.) : 0 for all hours
Channel setting
Specify PI1
■
Logging pulse counts for every day, resetting at 0 hour
SETTING DIALOG
PARAMETER
DESCRIPTION
AI1
CH setting
Time
Time input
Hour
Alarm zone setting
Partitions : 2
Zone 1 upper limit = Zone 2 lower limit = 2
PI Reset : Reset PI1 in Zone 1
PI1
Assign the relevant pulse input channel.
Data logging
Storing rate time unit
Hour
Storing rate (hour)
Hour : Check 00.
Offset (min.) : 0
Offset (sec.) : 0
Channel setting
Specify PI1
NOTE
• Refer to 11. LOGGING FUNCTION (TYPE C, D & E) for detailed data logging setting.