R7I4DECT-1-PA8A
5-2-55, Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN
Phone: +81(6)6659-8201 Fax: +81(6)6659-8510 E-mail: info@m-system.co.jp
EM-7779-F Rev.1 P. 2 / 11
COMPONENT IDENTIFICATION
■
FRONT VIEW
Fixed Address Setting Rotary SW
Reset Input Connector
Status Indicator LEDs
RJ-45 Modular jack for
EtherCAT communication
PC Configurator Jack
ECT OU
T
ECT IN
CNFG.
X16
Dev. ID
PWR
RUN
ERR
L/A IN
L/A OUT
PI7
PI6
PI5
PI4
PI0
PI1
PI2
PI3
1
4
1
4
INPUT
X1
0 1 2
3
4
56
78
9A
B
C
D
EF
0 1 2
3
4
56
78
9A
B
C
D
EF
Pulse Input Terminals
RST
PI0 PI1 PI2 PI3 PI4 PI5 PI6 PI7
RST
Pulse Input
Status Indicator
LEDs
Reset Input
Status Indicator
LED
Terminals for
power supply &
sensor excitation
■
STATUS INDICATOR LED
ID
FUNCTION
COLOR STATUS
Power
Internal power
Green
Off
Error
On
Normal
RUN
Device state
Green
Off
INIT
Blinking
PRE-OPERATIONAL
Single Flash
SAFE-OPERATIONAL
On
OPERATIONAL
ERR
Error
Red
Off
No error
Blinking
Invalid Configuration
Single Flash
Local error
Double Flash
Process data watchdog timeout/
EtherCAT watchdog timeout
On
Application controller failure
L/A IN
IN port status
Green
Off
No Link
Flickering
Link and activity
On
Link without activity
L/A OUT
OUT port status
Green
Off
No Link
Flickering
Link and activity
On
Link without activity
Blinking
200ms-On, 200ms-Off
Single flash
200ms-On, 1000ms-Off
Double flash
200ms-On, 200ms-Off, 200ms-On, 1000ms-Off
Flickering
50ms-On, 50ms-Off
■
FIXED ADDRESS SETTING ROTARY SW (ID selector)
Fixed address 1 to 255 can be set using the two rotary switches each marked 0 to F in combination.
When fixed address is not used, set the switches to 0.
Settable range: 0 to 255
Factory default: 0
Fixed Address Setting (x1)
Fixed Address Setting (x16)
0123
45
678
9AB
C
D
EF
0123
45
678
9AB
C
D
EF