background image

R7I4DECT-1-PA8A

5-2-55, Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN
Phone: +81(6)6659-8201  Fax: +81(6)6659-8510  E-mail: info@m-system.co.jp

EM-7779-F  Rev.1  P. 9 / 11

 

Sync Manager Type (0x1C00)

Sync Manager Type is allocated to object 0x1C00 based on the EtherCAT specification.

Table 7: Object Configuration For Sync Manager Type

INDEX

SUB-INDEX

DATA TYPE

BIT

ACCESS

VALUE

CONTENT

0x1C00

0

UINT8

8

RO

4

Number of items

1

UINT8

8

RO

1

Mailbox Write 

2

UINT8

8

RO

2

Mailbox Read 

3

UINT8

8

RO

3

Process Output Data 

4

UINT8

8

RO

4

Process Input Data 

 

Sync Manager Parameter Objects (0x1C32, 0x1C33)

In R7I4DECT, objects 0x1C32 and 0x1C33 do not exist, as the value of Sync Manager Parameter is fixed.
R7I4DECT supports Free Run mode only as the Sync mode. 
Note that Distributed Clock (DC) mode is not supported.

 

Device Type (0x1000)

The device type of this unit is allocated to object 0x1000.  The device type is 5001.

Table 8: Object Configuration For Device Type

INDEX

DATA TYPE

BIT

ACCESS

VALUE

CONTENT

0x1000

UINT32

32

RO

5001

Device type

 

Error Register (0x1001)

R7I4DECT does not use Object 0x1001.

 

Manufacturer Device Name (0x1008)

The device name is allocated to object 0x1008 in String form.

Table 9: Object Configuration For Device Name

INDEX

DATA TYPE

BIT

ACCESS

VALUE

CONTENT

0x1008

STRING

32

RO

R7I4DECT-1-PA8A

Model number

 

Manufacturer Hardware Version (0x1009)

The hardware device version of this unit is allocated to object 0x1009 in String form.
The format of version is “n.nn.”

Table 10: Object Configuration For Hardware Version

INDEX

DATA TYPE

BIT

ACCESS

VALUE

CONTENT

0x1009

STRING

32

RO

n.nn

Hardware version

 

Manufacturer Software Version (0x100A)

The software version of this unit is allocated to object 0x100A in String form.
The format of version is “n.nn.”

Table 11: Object Configuration For Software Version

INDEX

DATA TYPE

BIT

ACCESS

VALUE

CONTENT

0x100A

STRING

32

RO

n.nn

Software version

Summary of Contents for EtherCAT R7I4DECT-1-PA8A

Page 1: ...o the whole system and employ additional protective measures to ensure the CE conform ity POWER INPUT RATING OPERATIONAL RANGE Locate the power input rating marked on the product and confirm its opera...

Page 2: ...rmal RUN Device state Green Off INIT Blinking PRE OPERATIONAL Single Flash SAFE OPERATIONAL On OPERATIONAL ERR Error Red Off No error Blinking Invalid Configuration Single Flash Local error Double Fla...

Page 3: ...relevant to the pin number of the unit Perform wiring according to this instruction manual PULSE INPUT TERMINAL ASSIGNMENTS e CON connector Recommended cable connector 37104 000FL 3M Company does not...

Page 4: ...ling edge DI ON Edge direction for resetting pulse count by reset terminal Falling edge DI ON Rising edge DI OFF Falling edge DI ON Enabling or disabling pulse count reset by reset terminal Enable or...

Page 5: ...TION DIAGRAM Note In order to improve EMC performance bond the FE terminal to ground Caution FE terminal is NOT a protective conductor terminal SNSR EXC SNSR EXC FE PWR PWR 1 2 4 5 3 POWER SUPPLY IN S...

Page 6: ...an 0 the designated address is written in the resistor 0x0012 of ESC EtherCAT Slave Controller when R7I4DECT starts up Data Configuration Data are configured in accordance with the EtherCAT Modular De...

Page 7: ...BOOT state not supported 0x0016 Invalid MailBox configuration PREOP 0x0017 Invalid SyncManager configuration 0x001B SyncManager Watchdog Timeout 0x001D Invalid Output Configuration 0x001E Invalid Inp...

Page 8: ...vely In the data of RxPDO and TxPDO index sub index and the number of bit of each object which is referred to are stored For input data each object with the address starting with 0x6000 is referred to...

Page 9: ...it is allocated to object 0x1000 The device type is 5001 Table 8 Object Configuration For Device Type INDEX DATA TYPE BIT ACCESS VALUE CONTENT 0x1000 UINT32 32 RO 5001 Device type Error Register 0x100...

Page 10: ...onsists of 8 digits starting with two alpha numeral characters followed by six numeral characters The serial number is expressed as 32 bit data divided into 6 bit 6 bit and 20 bit groups with the firs...

Page 11: ...eset bit CH2 Pulse count preset bit CH3 Pulse count preset bit CH7 Pulse count preset bit CH4 Pulse count preset bit CH5 Pulse count preset bit CH6 Pulse count preset bit Unused PULSE COUNT RESET In n...

Reviews: