background image

5-2-55, Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN
Phone: +81(6)6659-8201  Fax: +81(6)6659-8510  E-mail: info@m-system.co.jp

EM-2666  Rev.2  P. 1 / 3

INSTRUCTION MANUAL

CURRENT LOOP SUPPLY

MODEL

M3DY

BEFORE USE ....

Thank you for choosing M-System.  Before use, please check 
contents of the package you received as outlined below.
If you have any problems or questions with the product, 
please contact M-System’s Sales Office or representatives.

 

PACKAGE INCLUDES:

Signal conditioner ...............................................................(1)

 

MODEL NO.

Confirm Model No. marking on the product to be exactly 
what you ordered.

 

INSTRUCTION MANUAL

This manual describes necessary points of caution when 
you use this product, including installation, connection and 
basic maintenance procedures.

POINTS OF CAUTION

 

CONFORMITY WITH EU DIRECTIVES

• 

This equipment is suitable for Pollution Degree 2 and In-
stallation Category II (transient voltage 2500V).  Rein-
forced insulation (signal input or output to power input: 
300V) and basic insulation (signal input to output: 300V) 
are maintained.  Prior to installation, check that the insu-
lation class of this unit satisfies the system requirements.

• 

Altitude up to 2000 meters.

• 

The equipment must be mounted inside a panel.

• 

The equipment must be installed such that appropriate 
clearance and creepage distances are maintained to con-
form to CE requirements.  Failure to observe these re-
quirements may invalidate the CE conformance.

• 

The actual installation environments such as panel con-
figurations, connected devices, connected wires, may af-
fect the protection level of this unit when it is integrated 
in a panel system.  The user may have to review the CE 
requirements in regard to the whole system and employ 
additional protective measures to ensure the CE conform-
ity.

• 

Install lightning surge protectors for those wires connect-
ed to remote locations.

 

POWER INPUT RATING & OPERATIONAL RANGE

• 

Locate the power input rating marked on the product and 
confirm its operational range as indicated below:

  100 – 240V AC rating: 90 – 264V, 47 – 66 Hz, approx. 3 – 5VA
  24V DC rating: 24V ±10%, approx. 2W
  24 – 240V DC rating: 21.6 – 264V, approx. 2W

 

GENERAL PRECAUTION

• 

Before you remove the unit or mount it, turn off the power 
supply and input signal for safety.

 

ENVIRONMENT

• 

Indoor use.

• 

When heavy dust or metal particles are present in the 
air, install the unit inside proper housing with sufficient 
ventilation.

• 

Do not install the unit where it is subjected to continuous 
vibration.  Do not subject the unit to physical impact.

• 

Environmental temperature must be within -20 to +55°C 
(-4 to 131°F) with relative humidity within 30 to 90% RH 
in order to ensure adequate life span and operation.

• 

Be sure that the ventilation slits are not covered with ca-
bles, etc.

 

WIRING

• 

Do not install cables close to noise sources (relay drive 
cable, high frequency line, etc.).

• 

Do not bind these cables together with those in which 
noises are present.  Do not install them in the same duct.

 

AND ....

• 

The unit is designed to function as soon as power is sup-
plied, however, a warm up for 10 minutes is required for 
satisfying complete performance described in the data 
sheet.

• 

With voltage output, do not leave the output terminals 
shortcircuited for a long time.  The unit is designed to 
endure it without breakdown, however, it may shorten ap-
propriate life duration.

COMPONENT IDENTIFICATION

Specifications
(side)

Body

Power LED

ZERO Adj

SPAN Adj

 

HOW TO SEPARATE THE EURO TYPE CONNECTOR 

TERMINAL BLOCKS

When you need to separate the euro type connector termi-
nal blocks from the transmitter body for wiring, insert a mi-
nus driver between the euro type connector terminal block 
and the housing body, pull up the driver and pull out the 
euro type connector terminal block.

Reviews: