INSTRUCTION MANUAL

LIGHTNING SURGE PROTECTOR

FOR DC POWER SUPPLY USE

MODEL

MDP-D

BEFORE USE ....

Thank you for choosing M-System.  Before use, please check 
contents of the package you received as outlined below.
If you have any problems or questions with the product, 
please contact M-System’s Sales Office or representatives.

 

PACKAGE INCLUDES:

Surge protector ....................................................................(1)
DIN rail mounting adaptor* ...............................................(1)
Screws for DIN rail mounting (M4 × 8)* ...........................(2)
*Included with option code /A33

 

MODEL NO.

Confirm Model No. marking on the product to be exactly 
what you ordered.

 

INSTRUCTION MANUAL

This manual describes necessary points of caution when 
you use this product, including installation, connection and 
basic maintenance procedures.

LIMITATION APPLICABLE TO M-RESTER

The M-RESTER will protect electronics equipment from 
damage caused by lightning by absorbing most of the 
surge voltages.
However, M-RESTER may not be effective against cer-
tain extremely high voltages caused by a direct or almost 
direct hit by lightning.
M-RESTER must be installed according to this installa-
tion / instruction manual.

GENERAL

 

FUNCTION & FEATURES

• Designed specifically for 12V/24V DC power supplies of 

small capacity

• Absorbs surges only without affecting instrumentation 

signal

• Monitor LED

 

SPECIFICATIONS

LINE TO LINE

LINE TO

EARTH

MDP-D12

MDP-D24

Max. continuous
operating voltage (Uc)

14V

27V

±160V

Voltage protection level (Up)

20V

40V

±650V

Leakage current

≤ 3mA

@14V DC

≤ 6mA

@27V DC

≤ 0.1mA

@±160V DC

Response time

≤ 4 nsec.

≤ 4 nsec.

≤ 20 nsec.

Max. line voltage

14V

27V

----

Max. discharge current (Imax) 

5000A (8 / 20 µs)

Nominal current (I

N

)

1A

Internal series resistance

≤ 0.6Ω including return

POINTS OF CAUTION

 

CONFORMITY WITH EU DIRECTIVES

• The actual installation environments such as panel con-

figurations, connected devices, connected wires, may af-
fect the protection level of this unit when it is integrated 
in a panel system.  The user may have to review the CE 
requirements in regard to the whole system and employ 
additional protective measures to ensure the CE conform-
ity.

 

ENVIRONMENT

• When heavy dust or metal particles are present in the 

air, install the surge protector inside proper housing with 
sufficient ventilation.

• Do not install the surge protector where it is subjected to 

continuous vibration.  Do not subject the unit to physical 
impact.

• Environmental temperature must be within -5 to +55°C     

(23 to 131°F) with relative humidity within 30 to 90% RH 
in order to ensure adequate life span and operation.

 

DIELECTRIC STRENGTH TEST

• Loosen the screw located at the left-center of the element 

and remove the element module from the base before 
conducting a dielectric strength testing.  Otherwise the 
element will start discharging at a voltage exceeding the 
max. continuous operating voltage (Uc), which can cause 
insulation failure of the module.

   Be sure to return the element and fasten securely after 

the test.

 

AND ....

• We recommend that you keep spare surge protectors so 

that you can replace them when necessary.

• Lightning surge can enter not only through power supply 

lines but also through signal lines.  We recommend that 
you also use the surge protectors for signal line for suffi-
cient protection.

COMPONENT IDENTIFICATION

Ground Terminal (G)
(used as mounting bracket)

Head Element

Base

Specifications

Monitor LED

Head Element is secured to Base 
with screw when the surge protector 
is shipped from Factory.

MODE

L