CHECKING ETHERNET CONNECTION

 

IP ADDRESS

This Tower Light does not support BootP Table Software.  The IP Address and Subnet Mask can be configured using the 
ITCFG Configurator Software.
The Modbus/TCP Port No. is fixed at 502.

 

CHECK WIRING

Connect an Ethernet cable to the RJ-45 connector.

 

CHECK INDICATOR

When wiring is correct, Link is turned on.

 

CHECK TOWER LIGHT CONNECTION

Enter “ping command” on the Windows MS-DOS as follows:
C:¥WINDOWS>ping ***.***.***.***
(***.***.***.***: Enter IP address in decimal.)
ping ***.***.***.*** with 32 bytes of data:
Reply from ***.***.***.*** : bytes = 32 time < 10ms TTL = 64
Reply from ***.***.***.*** : bytes = 32 time < 10ms TTL = 64
Reply from ***.***.***.*** : bytes = 32 time < 10ms TTL = 64
Reply from ***.***.***.*** : bytes = 32 time < 10ms TTL = 64
Ping statistics for ***.***.***.***
Packets: Sent = 4, Received = 4, Lost = 0 (0% loss)
Replies in case of normal connection are as shown above.  If the connection cannot be established normally due to e.g. wrong 
IP address, other replies such as ‘timeout’ will be received.

 

CHECK CONNECTION TO THE APPLICATION SOFTWARE

Check Point 1

: Link indicators

When normal connection is established, the front Link is turned on regardless of data sending/receiving status.  Check the 
network in case that the indicator is not on.

Check Point 2

: Run indicator

A green light turns on at the Run indicator in normal data sending/receiving.  

Check Point 3

: Link100 indicator

A green light blinks at the Link100 indicator in normal data sending/receiving for 100BASE link.